-
Unit Nine
Air Conditioning System
I.
Text
1. The meaning of air conditioning
An
air
conditioning
system
is
an
assembly
of
various
components
which
operate
in
a
controlled
manner
to
produce
a
specified condition of the air within a
space or building. To provide
complete
air
conditioning
a
system
must
accomplish
all
the
following:
heat,
humidify,
cool,
dehumidify,
ventilate,
filter,
and
circulate.
1.1 Comfort conditioning
The
design
specification
for
a
comfort
conditioning
system
is
intended
to
be
the
framework
for
providing
a
comfortable
environment for
human beings throughout the year, in the presence
of sensible heat gains in summer and
sensible heat losses in winter.
Dehumidification
would
be
achieved
in
summer
but
the
relative
humidity in the
conditioned space would be allowed to diminish as
winter
approached.
There
are
two
reasons
why
this
is
acceptable:
first,
human
beings
are
comfortable
within
a
fairly
large
range
of
humidity, from about 65 percent to
about 20 percent and, secondly,
if
single glazing is used it will cause the inner
surfaces of windows
to stream with
condensed moisture if it is attempted to maintain
too
high a humidity in
winter.
1
Thus, a
system
might be specified as capable of
maintaining an
internal
condition
of
22
℃
dry-bulb,
with
50
percent
saturation, in
the
presence
of
an
external
summer
state
of
28
℃
dry-bulb,
with
20
℃
wet-bulb,
declining
to
an
inside
condition
of
20
℃
dry-bulb,
with an
unspecified relative humidity, in the presence of
an external
state of
-2
℃
saturated in
winter.
1.2 Industrial
conditioning
Here
the
picture
is
quite
different.
An
industrial
or
scientific
process may,
perhaps, be performed properly only if it is
carried out
in an environment that has
values of temperature and humidity lying
within well defined limits. A departure
from these limits may spoil
the
work
being
done.
It
follows
that
a
choice
of
the
inside
design
condition
is
not
based
on
a
statistical
survey
of
the
feelings
of
human beings but on a
clearly defined statement of what is wanted.
Thus, a system might be specified to
hold 21
℃
±
0.5
℃
, with 50
percent saturation ±
2.5
percent, provided that the outside state lay
between 29.5
℃
dry-bulb, with 21
℃
wet- bulb
and
–
4
℃
saturated.
2. System Categories
Air
conditioning
systems
may
be
classified
as
central-station
or
unitary
systems.
A
central-station
system
is
one
in
which
the
components
of
the
system
are
all
grouped
together
in
one
central
mechanical
room
and
the
conditioned
air
is
sent
from
there
to
the
spaces to be conditioned through
extensive ductwork.
Unitary
systems
make
use
of
factory-assembled
and
tested
air
conditioning
units.
These
are
usually
installed
in
or
immediate
adjacent to a zone
or space to be conditioned. The source of the heat
and
the
refrigeration
may
be
in
each
air
conditioning
unit
or
in
a
“
central
”
mechanical room.
Another
possible
classification
divides
air
conditioning
systems
into cooling systems
and heating systems. Cooling systems may in
turn
to
be
classified
in
terms
of
the
cooling
medium
and
cooling
surface used. Heating systems are
classified as warm-air systems or
radiant-heat system.
The
basic systems and their several variants will be
discussed in
the following section.
2.1 Central-station System
A central-station year-
round air conditioning system is one which
usually
serves
a
single
large
building
or
space.
The
term
“
central-
station
”
is
ordinarily
not
applied
to
systems
of
less
than
about 25 tons of
cooling capacity, circulating about
10,000 cfm of
conditioning
air.
Buildings
whose
demand
is
less
than
this
are
usually
more
economically
air
conditioned
by
unitary
equipments,
all field-assembled.
A general arrangement of the component
parts of a central system
suitable
for
year-round
air
conditioning
with
close
control
of
temperature
and
humidity
is
illustrated
in
Figure
usually
consisted of following components:
(1) Coils for cooling and
dehumidifying, either for chilled water or
for direct expansion ofthe refrigerant
(2) Coils for heating, supplied with
steam or hot water
(3) Blower and
driving motor
(4) Sprays for cooling
and dehumidifying or for washing the air
(5) Air-cleaning equipment such as
filters, electrostatic precipitators,
odor-removing equipment, and germicidal
lamps
(6) A wide variety of control
devices.
Fig.9.1 Equipment Arrangement for
Central Systems
The
central-
station
air
conditioning
plant
must
be
supplied
with
either chilled water or refrigerant for
the cooling coils and with hot
water or
steam for the heating coils. Refrigeration
condensing units
and
steam
or
hot-water
boilers
for
these
purposes
may
be
in
the
same
mechanical
room
with
the
air
conditioner
or
may
be
in
an
adjoining room or in the
basement.
2.2 Capacity considerations.
It
will
be
recalled
that
heat
transfer
between
air
and
metal
surfaces
requires
rather
large
surfaces
areas.
Heating
and
cooling
coils
handling air at face velocities of around 500 fpm
must present
about 2 sq ft of face area
(four-row coil) for each 1,000 cfm of air
handled.
Physical
size
of
coil
filter
banks
is,
then,
one
of
the
limiting
factors
influencing
the
design
of
central-station
systems.
Space between
floors
of
a
building
usually
does
not
exceed
14
ft,
and
since
floor
area
utilized
is
a
justifiable
charge
against
the
operating expense of the
system, it is not good practice to expand
horizontally much beyond 12 to 14 ft,
which means that a practical
limitation
of somewhere around 40,000 cfm or 100 tons of
cooling
capacity is set for single air
conditioning
units
.
2
If the
job requires
more
total
capacity
than
this,
two
or
more
“
zones
”
should
be
planned
with
an
air
conditioning
system
installed
to
handle
each
zone.
Blowers
are
manufactured
commercially
in
capacities
up
to
200,000
cfm,
but
the
associated
equipment
for
units
handling
this
much air is heavy, difficult to
fabricate and install, and difficult to
service. Supply and return ductwork and
outside air intakes have to
be
extremely
large
for
units
handling
over
50,000
cfm,
and
the
problem
of
locating
these
ducts
in
the
building
structure
is
extremely difficult.
The nature of the building itself
frequently determines the extent
of
zoning to be specified, a theatre or department-
store installation,
where spaces of
large cubical content are the rule, may usually be
most
economically
conditioned
by
only
a
few
(perhaps
only
one)
central- station air
conditioning units. Office buildings, schools, and
similar buildings with many rooms lend
themselves to more zoning,
with
air
conditioning
units
of
10,000
to
30,000
cfm
being
in
common
use. As a general rule, considering all the
factors involved,
it
is
more
economical
to
pipe
chilled
water,
hot
water,
steam,
or
refrigerant to several smaller air
conditioning units than it is to erect
massive supply and return ducts to
serve the extended runs from one
extremely large
unit.
3
2.3 Filter
and mixing plenums
Return air and fresh
outside air should be brought into a plenum
for mixing prior to being filtered.
Motorized dampers usually central
the
amount of outside air introduced. The damper may
be controlled
by
a
thermostat
to
admit
less
outside
air
when
extreme
outdoor
temperatures
occur
or
by
smoke
and
odor-sensing
devices
in
the
conditioned space in order to increase
the amount of ventilation air
as
needed, owing to the nature of the occupancy.
Outside-air
quantity
should
periodically
be
markedly
increased
for
short
periods
of
time
in
all
buildings
to
prevent
a
situation from developing.
In seasons between heating and cooling,
it is desirable to operate on 100 per
cent outside air.
Filter banks are ordinarily assembled
vertically, and on large jobs
the
filters
are
usually
of
the
cleanable
type
for
use
over
and
over
again.
Disposable filters are occasionally used for
central system of
less
than
10,000
cfm
and
are
rather
universally
used
for
smaller
capacity unitary equipment.
2.4 Refrigeration and heating equipment
These
equipments
are
certainly
factors
in
the
design.
In
systems
requiring
only
one
or
two
zones,
where
the
air
conditioning
units
can be located close to the cooling and
heating equipment, the usual
practice
is
to
use
direct
expansion
refrigerant
coil
and
hot-water
coils. If, on the other hand, many
zones at remote locations are to be
served
by
a
single
cooling
and
heating
plant,
chilled
water
is
the
cooling medium circulated to the air
conditioning coils. Either hot
water
or
steam
may
be
used
as
the
heating
medium.
The
water
is
pumped to the mechanical
rooms which serve the several zones.
2.5 Always be insulated
The
entire housing for the central-station air
conditioning unit is
usually
insulated
over
its
outer-surface
with
at
least
l-in-thick
insulating
board.
All
steam,
hot
water,
chilled
water,
and
suction
refrigerant
piping
should
be
insulated
to
prevent
heat
losses
and
gains.
2.6 Noise and vibration
These
two
factors
are
of
extreme
importance.
If
air
conditioning
central systems are located on upper
floors, it must be ascertained
that
the
building
stress
design
has
taken
these
loads
into
account.
Quiet-operating
fan motors
should
be
specified,
vibration dampers
should
be
installed
under
all
rotating
equipment,
and
acoustic
linings specified
for mechanical rooms. Ducts and duct turns should
be
lined
at
critical
places
with
acoustic
board,
and
extreme
care
must
be exercised in duct design so that high velocity
whistle will
not occur. Selection of
grilles and registers must also be done with
great care or undue air noises will
result.
3. Unitary Air Conditioning
Systems.
There
are three broad categories of unitary systems: the
fan-coil
unit system, the duct-type
system, and the high-velocity conduit unit
system.
3.1 fan-coil unit
system
-
-
-
-
-
-
-
-
-
上一篇:新视野大学英语第三版视听说第二册答案
下一篇:商务术语