120KVA


UPS


操作说明



以下为设备自带英文操作说明:



A




Starting up sequence:


1)



Ensure that force transfer to bypass switch S4 is at


inverter



position.


2)



Ensure that Manual


Bypass Switch is at inverter/Static Bypass position and Total


Output


Breaker/Switch


is in



ON



position.


3)



Switch



ON




Bypass


Breaker/Switch


,


load


gets


connected


to


Bypass


through


Static


Switch


(Not applicable for system without bypass)


.


4)



Switch



ON




input


Breaker/Switch


,


dc


voltage


rises


and


inverter


gets



ON



.O bserve


output


output


voltage


on


display.


After


synchronization


load


gets


retransferred to inverter automatically.


5)



Observe


Battery


voltage


on


display,and


then


swtich



ON



Battery


Breaker/Switch


.


B)



Static bypass operation:


1)



In the event of failure of inverter, load gets transferred to Static Bypass


automatically.


2)



To put load on Static Bypass when inverter is



ON



, change force transfer to


bypass


switch


S4



from



inverter




to



Static


Bypass




position,


load


will


get


connected to Static Bypass.


C)



Manual bypass Operation:


1)



Change


force


transfer


to


Bypass


Switch


S4



from


Inverter




to



Static


Bypass




position.


(Not for applicable for system without bypass).



2)



Switch the Bypass Switch to Manual Bypass position.


3)



Switch



OFF



Output


Breaker/Switch.



D)



To shut down the system:


1)



Switch



OFF



Output


Breaker/switch


.


2)



Switch



OFF



Bypass


Breaker/switch


.


3)



Switch



OFF



Battery


Breaker/switch


.


4)



Switch



OFF



input


Breaker/switch


.


NOTE:


1.



Press reset switch to reset inverter fault.


2.



If system is without Bypass then do not follow bypass related instructions.


3.



If system is with only manual bypass, then do not follow static bypass related


instructions.


4.



connect same Bypass Source to UPS for all parallel & common bus systems.


For parallel systems operating instrutions will remains same as above.


Caution :


1.



Do


not


operate


Battery


Breaker/Switch


in


Mains


fail


or


Rectifier


trip


condition.


2.



Do


not


operate


inverter



ON/OFF< /p>



switch


from


mimic


Display


until


Output

-


-


-


-


-


-


-


-