厦门船舶重工股份有限公司



XIAMEN SHIPBUILDING INDUSTRY .




Ship name and No.: 408G


红宝石


3



Owner:


厦门轮总






: 2011.11.14




Emergency Diesel Engine Generator


应急发电机








Before and after the load test, the insulation measurement to be carried out for


all electrical equipment that this test concerns such as alternators and heaters

负载试


验前后应测量相关设备的绝缘,如发电机和加热器。



1. Alarm function


报警功能







Check and adjust the set value of pressure switches for alarm of lub. oil low


pressure by manually operated hydraulic pump. Check and adjust the set value of


temperature switches for alarm of cooling water high temperature and high


temperature by means of heating. Check the indication function of alarm on control


box at the engine while set the value of alarm. And check the proper function of


general alarm of emergency generator in monitoring system of ECR.







用手摇 液压泵校对并调定滑油低压报警压力开关的调定值。用加热法校对


并调定冷却水高温及滑 油温度高报警温度开关调整值。整定报警值同时,检查


机旁控制箱上报警显示功能,并检 查集控室内监控系统的应急发电机总故障报


警功能


.



2. Safety protection


安全保护功能







Make diesel generator over speed by artificial actuation. Check the function of


over speed and alarm for the stop by over speed. Over speed test carried out under


no load condition.


人为造成柴油机超速 ,检查超速功能,同时检查超速停车报


警功能。超速试验在没有负荷的状态下进行。






Safety alarm test for emergency generator


应急发电机安全报警试验



Test



Setting Point


Test result


Remark


Lub. Oil inlet pressure low alarm


Lub. Oil


outlet temp. high alarm



0.8bar±


0.2bar


116°



3


96°



3


2050r/min


--


--


--


--


--


--


0.8bar


115°


C


98°


C


OK


OK


OK


OK


OK


OK


OK





Simulation


Alarm No.20


Alarm No.23




Alarm No.37



Cooling water outlet temp. high alarm


Over speed (To AMS)


Common alarm (To AMS)


Batter failure


Fule oil leakage alarm


LAL of cooling water


E/G abnormal trip


Over current





3. Insulation resistance test


绝缘测试



Insulation resistance test in cold condition (M


Ω


) and hot condition(M


Ω


)


Item


Stator winding



Generator space heater



Cold condition


500


500


Hot condition


500


500







4. starting of emergency generator.


应急发电机的启动试验



emergency generator in cold condition. Check that it is stable and reliable


冷态启动应急发电机,检查启动是否平稳可靠














test and start fail alarm test with the first power source (battery).



第一能源(蓄电池)启动试验和启动失败报警试验










4.2.1. Charged batteries in sufficient time, start the diesel generator 3 times in cold


condition without recharging.

启动蓄电池充电之后,


中途不补充充电的情况下,


应能保证 冷态启动柴油机


3


次。



电瓶电压



25.8V



4.2.2. Make diesel generator fail to start 3 times by cutting off F.O. supply and giving


alarm


by the “START



FAILURE” on


control panel.



用切断燃油供给的方法使柴油发动机


3


次启动失败,


在控制板上来



START


FAILURE


”报警。





































4.3 Check reliability of the function for second power source (spring start motor). Start


the generator when cold with hand spring start motor no less than three times within


thirty minutes.



检查弹簧启动马达功能是否可靠(冷态)


,在


30


分钟内启动不少于

< p>
3


次。


























4.4 Under voltage trip test


欠压脱扣试验



Under no-load condition reduce revolution of prime mover quickly and drop the voltage


from 70% to 35% of rated value. Record low-voltage auto-trip value of generator.




空载状况下 快速降低柴油机的转速,使发电机电压从额定电压


70%


下降到


35%


,记录发电


机欠压自动脱扣值< /p>


.


第一次启动后电压



25.49V


第一次启动后电压



25.54V


第一次启动后电压



25.4V


Gen.




Em gen


Rated


Voltage


450V


Set


Point (V)


70%~35%


Delay


Time


9s


Remarks


207V


Result


OK


4.5 Short Time Delay


短延时脱扣




Gen.




Em gen


Rated


Current


192.5


Set


Point



A




575


Delay


Time



0.6s


Remarks


0.427s


Result


OK


4.6 Long Time Delay


长延时脱扣



Gen.




Em gen


Rated


Current


192.5


Set


Point



A




250


Delay


Time



30s


Remarks


19.7s


Result


OK




5. Characteristic test of emergency diesel generator set.


应急发电机的特性试验



5.1. V


oltage adjusting characteristic test at stable condition


稳态调压特性试验



Set the load and power factor of diesel generator to COS


φ


=1.0. Then characteristic


test at stable condition can be done.



During the variety of the load as following:0



25%



50%



75%



100%



75%



50%


25%



0, record the value of power, current, voltage and frequency at


different condition for generator. COS


φ


=1.0


Calculate the stable characteristic rate



V%=(V-Vn) / Vn x 100%


V:



voltage at different power


Vn:



rated voltage 450V


< br>V%



2.5%


Carry out the test with load variety for two times and record.


在柴油发电机的负载


和功率因数调整到


COS


φ


=1.0


后 ,


就可以进行稳态特性试验。在试验负载按下


列程序:


0



25%



50%



75%



100%



75%



50%



25%


0


变化时,记录个


工况下发电机 的功率,电流电压和频率值。


COS


φ


=1.0


计算稳态调整率




V%=(V-Vn) / Vn x 100%


V


是不同功率下的电压



Vn


是额定电压


450V



V%



2.5%



负载变化过程做二次试验并做记录



No.


Power


percentage


功率百分比



1


0%


2


3


4


5


6


7


50%


8


25%


9


0%


25%


50%


75%


100%


75%

-


-


-


-


-


-


-


-