Insulation Detection and Analysis of XLPE
Medium-Voltage Cables
Abstract:
The
polarization-depolarization
current
(PDC)
method
is
used
to
detect
the
insulation
status of medium
-voltage cables and the testing data are analyzed.
Thelow frequency component
of
depolarization current, which is relatively less
sensitive to the cable length, is used to overcome
the impact of cable length. Cable aging
status is determined through analyzing the value
range of
the depolarization current ’s
low frequency components,the average discharge
rate and the impact
of
different
polarization
time.
Finally,
this
method
is
applied
in
repaired
cables
and
it
is
verifiedthat the characteristics of the
repaired cable is close to that of new cable with
same length,
which shows that the
method can be used for identification of the
cable’s aging status.
Key
words:
medium-
voltage
cable;
insulation
detection;
polarization
and
depolarization
(PDC)
method
0
introduction
Cross-linked
polyethylene
(XLPE
)
power
cable
has
been
widely
used
due
to
its
realiable
[1]
dielectric
and
mechanical
properties
.
The
insulation
of
the
cable
is
greatly
damaged
by
[2]
electricity
tree and water tree generated in the long
operation
.
Power
outage caused by insulation
aging
could
cause
great
economic
losses,
which
requires
the
detection
of
the
cable
insulation
condition.
The
PDC method is a method of detecting a large
segment of the overall performance
[3-4]
of
the
cable
.
The
measuring
instrument
used
is
simple,
lightweight,
and
the
method
can
effectively detect the cable insulation
performance in a variety of reasons
.
1 Fundamentals of Polarization -
depolarization current method
Charging the tested cable by a constant
voltage source,then a charging current
ich
is generated,
after a
long charge time we can obtain a steady-state
current
idc
. After a time
of
t
, switch off the
voltage
power
to
discharge,
and
a
discharge
current
idisch
is
generated(
idisch
'
is
merely
the
discharge current with
polarity reversed and shifted backward in timeline
by
t
), and then after a
sufficiently
long
discharge,
the
current
will
be
reduced
to
know
the
charging
and
discharging
process
are
related
to
electrical
characteristics
of
the
power
as
well
as
the
supply
voltage, so we can analyze
ich
and
idisch
to determine the electrical
characteristics of the cable,
and
then
to
determine
whether
the
tested
is
excessively
aging.
Current
variation
in
PDC
measurement shown in FIG. 1
2 Measuring circuit and measurement
procedures
PDC measurement circuit
structure shown in Figure 2
.Charging
the tested cable by connected
the high-
voltage interrupter switch to the voltage source.
After a period of polarization switch to
connect KEYTHLEY 6485. We can use
KEYTHLEY648 to observe and record depolarizing
current,
then transmit the information
to a computer for analysis.
Fig.1 Current variation
Fig.2 Circuit
schematic
Fig.3 The depolarization
currents
-
-
-
-
-
-
-
-
-