-
NFPA 13D
Standard for the
Installation of Sprinkler
Systems
in
One-
and
Two-Family Dwellings
and
Manufactured Homes
1999
Edition
Copyright
?
1999 NFPA, All Rights
Reserved
This edition of NFPA 13D,
Standard for the Installation of
Sprinkler Systems in One- and Two-
Family Dwellings and
Manufactured
Homes
, was prepared by the Technical
Committee
on Residential Sprinkler
Systems, released by the Technical
Correlating Committee on Automatic
Sprinkler Systems, and
acted on by the
National Fire Protection Association, Inc.,
at its May Meeting held May 17-20,
1999, in Baltimore, MD.
It
was
issued
by
the
Standards
Council
on
July
22,
1999,
with
an effective date of August 13, 1999,
and supersedes all
previous editions.
Changes
other
than
editorial
are
indicated
by
a
vertical
rule
in the margin of the pages on which
they appear. These lines
are
included
as
an
aid
to
the
user
in
identifying
changes
from
the previous edition.
This
edition
of
NFPA
13D
was
approved
as
an
American
National
Standard on August 13, 1999.
Origin and Development of NFPA 13D
Recognizing
the
need
to
reduce
the
annual
life
loss
from
fire
in residential occupancies (about 50
percent of total loss
of life by fire),
the Committee on Automatic Sprinklers
appointed
a
subcommittee
in
May
1973
to
prepare
the
Standard
on the Installation
of Sprinkler Systems in One- and
Two-
Family Dwellings and Mobile Homes
. The
subcommittee was
composed
of
members
of
the
Committee
on
Automatic
Sprinklers
and other technically competent
experts. The standard was
submitted
and
adopted
at
the
NFPA
Annual
Meeting
in
Chicago,
IL, on May 12-16,
1975.
The 1980
edition
was a complete
rewrite of
the
1975 edition,
including SI units where appropriate.
The 1980 edition
incorporated the
results of the residential sprinkler test
program administered by the National
Fire Protection
Association and funded
by a research grant from the United
States Fire Administration. Factory
Mutual Research
Corporation and the Los
Angeles City Fire Department
conducted
the dwelling tests. Factory Mutual Research
Corporation,
McNeary
Insurance Consulting Services, and
the
Charlotte, North
Carolina, Fire Department conducted the
mobile home tests.
After
gaining practical experience using the 1980
edition,
modifications to the standard,
including removal of design
parameters
for dry pipe systems, were made in the 1984
edition.
The 1989 and 1991
editions established criteria for the use
of antifreeze systems as well as some
of the installation
criteria
associated with specially
listed
piping
materials.
The
1994
edition
provided
expanded
information
on
nonmetallic
pipe and
introduced a new design option that reduced water
storage requirements for limited area
dwellings.
The 1996 edition of the
standard included expanded
information
on the use and placement of residential
sprinklers
near
heat
sources.
For
the
first
time
since
1941,
the
use of
1
/
2
-in. (12.7-mm) piping material was
permitted
again for sprinkler systems
under specific conditions. A
number
of
appendix
figures
were
also
added
to
address
methods
for protecting pipe
from freezing in unheated attics.
The
1999 edition revises criteria for certain types of
multipurpose
piping
systems
and
adds
requirements
to
mitigate
the effect of water
softeners and filters on system
performance.
Information
on
the
application
of
solvent
cement
for nonmetallic piping systems has been
provided and the
exception
for
omitting
sprinkler
coverage
in
attics
and
crawl
spaces has been
modified.
Technical Correlating
Committee on Automatic Sprinkler
Systems (AUT-AAC)
John G.
O’Neil
l,
Chair
Gage-Babcock & Assoc. Inc., VA [SE]
Milosh T. Puchovsky,
Nonvoting Secretary
Nat’l
Fire Protection Assn., MA
Jose R. Baz,
Int’l Engineered Systems, LTD, Inc., FL
[M]
Rep. NFPA Latin American
Section
Kerry M. Bell,
Underwriters Laboratories Inc., IL [RT]
Eric H. Cote,
Rolf Jensen &
Assoc., Inc., MA [SE]
Russell P.
Fleming,
Nat’l Fire
Sprinkler Assn., NY [M]
Joseph B. Hankins, Jr.,
Factory Mutual Research Corp., MA
[I]
Roland J. Huggins,
American
Fire Sprinkler Assn., Inc., TX
[IM]
Sultan M. Javeri,
Protection Int’l, Ltd, France
[I]
Andrew
Kim,
Nat’l
Research
Council
of
Canada,
ON,
Canada
[RT]
Gerald R. Kirby,
Marriott Int’l, Inc., DC [U]
Rep. American Hotel & Motel Assn.
B. J. Lukes,
Grinnell Fire
Protection System Co. Ltd/Tyco,
Canada
[M]
Rep. Canadian Automatic Sprinkler
Assn.
Joseph W. Noble,
Clark
County Fire Dept., NV [E]
Donald R.
Oliver,
Wilson Fire/Rescue Services, NC
[E]
Rep. Int’l Assn. of Fire
Chiefs
James
Retzloff,
The Viking Corp., MI [M]
Chester W. Schirmer,
Schirmer Engr Corp., NC [SE]
John Nigel
Stephens,
Loss Prevention Council,
England [I]
Lynn K.
Underwood,
Wausau HPR Engr, WI [I]
John J. Walsh,
UA Joint
Apprenticeship Committee Local 669,
MD
[L]
Rep.
United
Assn.
of
Journeymen/Apprentices
of
Plumbing/Pipe
Fitting
Alternates
Donald
“Don” D. Becker,
Midland
Automatic Sprinkler Co.,
Inc., MO [IM]
(Alt. to R. J. Huggins)
Raymond A. Grill,
Rolf
Jensen & Assoc., Inc., VA [SE]
(Alt. to
E. H. Cote)
Kenneth E.
Isman,
Nat’l Fire Sprinkler
Assn., NY [M]
(Alt. to R. P.
Fleming)
George E. Laverick,
Underwriters Laboratories Inc., IL [RT]
(Alt. to K. M. Bell)
Donato
A.
Pirro
E.,
Electro
Sistemas
De
Panama,
S.A.,
Panama
[M]
(Alt.
to J. R. Baz)
William E.
Wilcox,
Factory Mutual Research Corp.,
MA [I]
(Alt. to J. B. Hankins, Jr.)
Nonvoting
Edward K.
Budnick,
Hughes Assoc., Inc., MD [SE]
Rolf H. Jensen,
Belleair, FL
[SE]
(Member Emeritus)
William E. Koffel, Jr.,
Koffel Assoc. Inc., MD [SE]
Kenneth W.
Linder,
HSB Industrial Risk Insurers,
CT [I]
Christopher T.
Lummus,
Insurance Services Office,
Inc., TX
[I]
Daniel
Madrzykowski,
U.S. Nat’l
Inst. of Standards &
Technology, MD
[RT]
Peter Papavasiliou,
Engr Professionals, Ltd, IL [SE]
J.
William Sheppard,
General Motors Corp.,
MI [U]
Milosh T. Puchovsky,
NFPA Staff Liaison
This
list
represents
the
membership
at
the
time
the
Committee
was
balloted
on
the
text
of
this
edition.
Since
that
time,
changes
in
the
membership
may
have
occurred. A
key to classifications is found
at
the
back of
this document.
NOTE:
Membership
on
a
committee
shall
not
in
and
of
itself
constitute
an
endorsement
of
the
Association
or
any
document
developed
by
the
committee
on
which
the member serves.
Committee Scope:
The
committee shall have overall
responsibility for documents that
pertain to the
criteria for the design
and installation of
automatic, open and
foam-water sprinkler systems,
including
the character and adequacy of water
supplies,
and
the
selection
of
sprinklers,
piping,
valves, and all materials and
accessories. This
committee does not
cover the installation of fire
pumps,
nor the construction and installation of
gravity and pressure tanks and towers,
nor the
installation, maintenance, and
use of central
station, proprietary,
auxiliary, and local
signaling systems
for watchmen, fire alarm,
supervisory
service, nor the design of fire
department hose connections.
Technical Committee on Residential
Sprinkler Systems
(AUT-RSS)
Daniel Madrzykowski,
Chair
U.S. Nat’l Inst. of
Standards & Technology, MD [RT]
George W. Baker,
Mashpee
Fire & Rescue Dept., MA [E]
Rep. Int’l
Assn. of Fire
Chiefs
Frederick J. Benn,
Advanced
Automatic Sprinkler, Inc., CA
[IM]
Frederick C. Bradley,
Gage-
Babcock & Assoc. Inc., GA [SE]
Lawrence
Brown,
Nat’l Assn. of Home
Builders, DC [U]
Edward K.
Budnick,
Hughes Assoc., Inc., MD [SE]
Brian Hoening,
Globe Fire
Sprinkler Corp., MI [M]
Rep. Nat’l Fire
Sprinkler Assn.
Kenneth E.
Isman,
Nat’l Fire Sprinkler
Assn., NY [M]
Hsiang-Cheng
Kung,
Factory Mutual Research Corp., MA
[I]
George E. Laverick,
Underwriters Laboratories Inc., IL [RT]
Tom Lawrence,
Smith Fire
Sprinkler Co., Inc., FL [IM]
Rep.
American Fire Sprinkler Assn., Inc.
John C. Livingston, Jr.,
Livingston Fire Protection, Inc.,
MD
[IM]
Rep. Nat’l Fire Sprinkler
Assn.
Raymond H.
Lower,
Cigna Loss Control Services, WA
[I]
Rep. American Insurance Services
Group, Inc.
M.
L.
“Larry”
Maruskin,
Federal
Emergency
Mgmt.
Agency,
MD
[C]
Michael
Nelson,
Rolf Jensen & Assoc., Inc., NY
[SE]
Ronald G. Nickson,
Nat’l Multi Housing Council, DC
[U]
Maurice M.
Pilette,
Mechanical Designs Ltd., MA
[SE]
Chester W. Schirmer,
Schirmer Engr Corp., NC [SE]
Sandra
Stanek,
Rural Metro Fire Dept., AZ [E]
Donald Townley,
B. F.
Goodrich, OH [M]
Rep. Committee for
Firesafe Dwellings
John J.
Walsh,
UA Joint Apprenticeship
Committee Local 669,
MD [L]
Rep.
United
Assn.
of
Journeymen/Apprentices
of
Plumbing/Pipe
Fitting
Susan J.
Weigand,
Victory Fire Protection, Inc.,
PA [IM]
Rep. American Fire Sprinkler
Assn., Inc.
Alternates
Carl
F. Baldassarra,
Schirmer Engr Corp., IL
[SE]
(Alt. to C. W. Schirmer)
Phillip
A.
Brown,
American
Fire
Sprinkler
Assn.,
Inc.,
TX
[IM]
(Alt. to S. J. Weigand)
William M. Carey,
Underwriters Laboratories Inc., IL [RT]
(Alt. to G. E. Laverick)
Thomas Deegan,
Viking Corp.,
MI [M]
(Alt. to B. Hoening)
Gary L. Johnson,
B. F.
Goodrich, OH [M]
(Alt. to D. Townley)
John C. McDonald,
Virginia
Sprinkler Co., Inc., VA [IM]
(Alt. to
T. Lawrence)
Michael
A.
Rothmier,
UA
Joint
Apprenticeship
Committee
Local
669, MD [L]
(Alt. to J. J.
Walsh)
Harry Shaw,
Harry
Shaw & Assoc. Inc., MD [E]
(Alt. to G.
W. Baker)
George Stanley,
Wiginton Fire Sprinklers, FL [IM]
(Alt.
to J. C. Livingston, Jr.)
David
W.
Stroup,
U.S.
Nat’l
Inst.
of
Standards
&
Technology,
MD [RT]
(Alt. to D. Madrzykowski)
Richard
E.
Thonnings,
American
Insurance
Services
Group,
Inc.,
NY [I]
(Alt. to R. H. Lower)
Randolph W. Tucker,
Rolf
Jensen & Assoc., Inc., TX [SE]
(Alt. to
M. Nelson)
Terry L. Victor,
Tyco Int’l, Ltd, MD [M]
(Alt. to K. E. Isman)
Bennie
Vincent,
Factory Mutual Research Corp.,
MA [I]
(Alt. to H. Kung)
Joseph Wiehagen,
Nat’l Assn. of Home Builders, MD
[U]
(Alt. to L. Brown)
Nonvoting
Rohit
Khanna,
U.S.
Consumer
Product
Safety
Commission,
MD
[C]
Milosh T.
Puchovsky,
NFPA Staff Liaison
This
list
represents
the
membership
at
the
time
the
Committee
was
balloted
on
the
text
of
this
edition.
Since
that
time,
changes
in
the
membership
may
have
occurred. A
key to classifications is found
at
the
back of
this document.
NOTE:
Membership
on
a
committee
shall
not
in
and
of
itself
constitute
an
endorsement
of
the
Association
or
any
document
developed
by
the
committee
on
which
the member serves.
Committee Scope:
The
committee shall have primary
responsibility for documents on the
design and
installation of automatic
sprinkler systems in
dwellings and
residential occupancies up to and
including four stories in height,
including the
character and adequacy of
water supplies, and the
selection of
sprinklers, piping, valves and all
materials and accessories.
NFPA 13D
Standard for the
Installation of Sprinkler Systems in
One- and Two-Family
Dwellings and
Manufactured Homes
1999 Edition
NOTICE: An asterisk (*)
following the number or letter
designating a paragraph indicates that
explanatory
material on the paragraph
can be found in Appendix A.
Information on referenced publications can be
found in
Chapter 6 and Appendix B.
Preface
It is intended that
this standard provide a method for
those individuals wishing to install a
sprinkler system
for
additional
life
safety
and
property
protection.
It
is
not the
purpose of this standard to require the
installation of an automatic sprinkler
system. This
standard
assumes
that
one
or
more
smoke
detectors
will
be
installed
in
accordance
with
NFPA
72,
National
Fire
Alarm
Code
?
.
Chapter 1 General Information
1-1* Scope.
This
standard
covers
the
design
and
installation
of
automatic
sprinkler
systems
for
protection
against
the
fire
hazards
in
one- and two-family
dwellings and manufactured homes.
1-2*
Purpose.
The
purpose
of
this
standard
is
to
provide
a
sprinkler
system
that aids in the
detection and control of residential fires
and thus provides improved protection
against injury, life
loss, and property
damage. A sprinkler system designed and
installed in accordance with this
standard is expected to
prevent
flashover (total involvement) in the room of fire
origin, where sprinklered, and to
improve the chance for
occupants to
escape or be evacuated.
Guidelines have
been established for the design and
installation of sprinkler systems for
one- and two-family
dwellings and
manufactured homes. Nothing in this standard
is intended to restrict new
technologies or alternative
arrangements, provided that the level
of safety prescribed
by the standard is
not reduced.
1-3 Definitions.
Approved.*
Acceptable to
the authority having
jurisdiction.
Authority
Having
Jurisdiction.*
The
organization,
office,
or
individual responsible for approving
equipment, materials,
an installation,
or a procedure.
Check Valve.
A valve
that allows
flow
in one direction
only.
Control
Valve.*
A valve employed to control
(shut) a supply
of water to a sprinkler
system.
Design
Discharge.
The
rate
of
water
discharged
by
an
automatic
sprinkler
expressed in gpm (L/min).
Dry
System.
A
system
employing
automatic
sprinklers
attached
to
a
piping
system
containing
air
under
atmospheric
or
higher
pressures. Loss of pressure from the
opening of a sprinkler
or
detection
of a fire
condition causes the release of
water
into the piping system and out the
opened sprinkler.
Dwelling.
Any
building
that
contains
not
more
than
one
or
two
dwelling units intended
to be used, rented, leased, let, or
hired out to
be occupied or
that are
occupied for
habitation
purposes.
Dwelling
Unit.
One
or
more
rooms,
arranged
for
the
use
of
one
or more
individuals living together, as in a single
housekeeping unit, that normally have
cooking, living,
sanitary, and sleeping
facilities.
Labeled.
Equipment or materials to which has been attached
a
label,
symbol,
or
other
identifying
mark
of
an
organization
that is
acceptable to the authority having jurisdiction
and
concerned with product evaluation,
that maintains periodic
inspection of
production of labeled equipment or materials,
and by whose labeling the manufacturer
indicates compliance
with appropriate
standards or performance in a specified
manner.
Listed.*
Equipment,
materials,
or
services
included
in
a
list
published by an
organization that is acceptable to the
authority having jurisdiction
and concerned
with
evaluation
of products or
services, that maintains periodic inspection
of production of listed equipment or
materials or periodic
evaluation
of
services,
and
whose
listing
states
that
either
the equipment,
material, or service meets appropriate
designated standards or has been tested
and found suitable
for a specified
purpose.
Manufactured
Home.*
A
structure,
transportable
in
one
or
more
sections, that in the
traveling mode is 8 body ft (2.4 m) or
more
in
width
and
40
body
ft
(12
m)
or
more
in
length
or,
where
erected
on-site,
is
320
ft
2
(28
m
2
)
or
more,
and
that
is
built
on a
permanent chassis and designed to be used as a
dwelling
with
or
without
a
permanent
foundation
where
connected
to
the
required
utilities, and includes the plumbing, heating, air
conditioning, and electrical systems
contained therein.
Multipurpose
Piping
System.
A
piping
system
within
dwellings
and manufactured homes intended to
serve both domestic and
fire protection
needs.
Preengineered
System.
A
packaged
sprinkler system
including
all
components
connected
to
the
water
supply
and
designed
to
be
installed according to pretested limitations.
Pump.
A mechanical device
that transfers or raises, or
transfers
and raises, the pressure of a fluid (water).
Residential Sprinkler.
A
type of sprinkler that meets the
definition of fast response as defined
by NFPA 13,
Standard
for
the
Installation
of
Sprinkler
Systems
,
and
that
has
been
specifically investigated for its
ability to enhance
survivability in the
room of fire origin and that is listed
for use in the protection of dwelling
units.
Shall.
Indicates a
mandatory requirement.
Should.
Indicates a
recommendation or that which is advised
but not required.
Sprinkler,
Automatic.
A fire suppression or
control device
that operates
automatically when its heat-actuated element
is heated to its thermal rating or
above, allowing water to
discharge over
a specific area.
Sprinkler
System.
An integrated system of piping,
connected
to
a
water
supply,
with
listed
sprinklers
that
automatically
initiate water
discharge over a fire area. Where required,
the sprinkler system also includes a
control valve and a
device for
actuating an alarm when the system operates.
Standard.
A document, the
main text of which contains only
mandatory provisions using the word
“shall” to indicate
requirements and
which is in a form generally suitable for
mandatory reference by another standard
or code or for
adoption into law.
Nonmandatory provisions shall be located
in an appendix, footnote, or fine-print
note and are not to
be considered a
part of the requirements of a standard.
Supply Pressure.
The
pressure within the supply (e.g., city
or private supply water source).
System
Pressure.
The
pressure
within
the
system
(e.g.,
above
the
control valve).
System Working
Pressure.
The maximum anticipated
static
(nonflowing)
or
flowing
pressure
applied
to
sprinkler
system
components exclusive of surge
pressures.
Waterflow Alarm.
A sounding device activated by a waterflow
detector
or alarm check
valve and arranged to
sound an
alarm
that is audible in all
living areas over background noise
levels with all intervening doors
closed.
Waterflow
Detector.
An
electric
signaling
indicator
or
alarm
check valve actuated
by waterflow in one direction only.
Wet
System.
A
system
employing
automatic
sprinklers
that
are
attached
to a piping system containing water and connected
to a water supply so that water
discharges immediately from
sprinklers
opened by a fire.
1-4* Maintenance.
The owner is responsible for the
condition of a sprinkler
system and
shall keep the system in normal operating
condition.
1-5 Devices,
Materials, Design, and Installation.
1-5.1*
Only new
residential sprinklers shall be employed in the
installation of sprinkler
systems.
1-5.2
Only
listed
and
approved
devices
and
approved
materials
shall
be used in sprinkler
systems.
Exception: Listing
shall
be
permitted
to
be
waived
for
tanks,
pumps, hangers, waterflow detection
devices, and waterflow
valves.
1-5.3
Where
listed,
preengineered
systems
shall
be
installed
within
the limitations that have been
established by the testing
laboratories.
1-5.4*
All
systems shall be tested for leakage at normal
system
operating water
pressure.
Exception: Where
a fire department pumper connection is
provided, hydrostatic pressure tests
shall be provided in
accordance with
NFPA 13, Standard for the Installation of
Sprinkler Systems.
1-5.5
Where
solvent
cement
is
used
as
the
pipe
and
fittings
bonding
agent,
sprinklers
shall
not
be
installed
in
the
fittings
prior
to the fittings being
cemented in place.
1-6*
Units.
Metric units of measurement in
this standard shall be in
accordance
with the modernized metric system known as the
International System of Units (SI). The
liter and bar units
are outside of, but
recognized by, SI and are commonly used
in international fire protection. These
units are provided
in Table 1-6 with
their conversion factors.
Table 1-6
Metric Conversions
Name of
Unit
liter
pascal
bar
bar
Unit Symbol
L
Pa
bar
bar
Conversion
Factor
1
gal = 3.785 L
1
psi = 6894.757 Pa
1 psi = 0.0689 bar
1 bar = 105 Pa
1-6.1
Where a
value for measurement as specified in this
standard
is
followed by
an equivalent value in
other
units, the
first
stated value shall be regarded as the
requirement. A given
equivalent value
shall be considered to be approximate.
1-6.2
SI units
have been converted by multiplying the quantity by
the conversion factor and then rounding
the result to the
appropriate number of
significant digits.
Chapter
2 Water Supply
2-1 General Provisions.
Every automatic sprinkler system shall
have at least one
automatic
water
supply.
Where
stored
water
is
used
as
the
sole
source
of
supply,
the
minimum
quantity
shall equal
the
water
demand
rate times 10 minutes.
(See 4-1.3.)
Exception: For dwelling units that are
one story in height
and
less
than
2000
ft
2
(186
m
2
)
in
area,
the
water
supply
shall
be
at least 7 minutes for the two-sprinkler demand.
2-2* Water Supply Sources.
The
following
water
supply
sources
shall
be
considered
to
be
acceptable by this standard:
(1)
A connection to a
reliable waterworks system with or
without an automatically operated pump
(2)
An elevated tank
(3)
A
pressure
tank
designed
to
American
Society
of
Mechanical
Engineers (ASME) standards for a
pressure vessel with a
reliable
pressure source
(4)
A
stored
water
source
with
an
automatically
operated
pump
2-3* Multipurpose
Piping System.
A piping system serving
both sprinkler and domestic needs
shall
be considered to be acceptable by this standard
where
the following conditions are met.
(a)
*
In
common
water
supply
connections
serving
more
than
one
dwelling
unit,
5
gpm
(19
L/min)
are
added
to
the
sprinkler
system
demand to
determine the size
of common
piping
and
the
size of
the total water supply requirements.
Exception: Domestic design demand
shall not be required to
be added where
provision is made to prevent flow into the
domestic water system upon operation of
a sprinkler.
(b)
Smoke
detectors are provided in accordance with NFPA
72,
National Fire Alarm
Code
?
.
(c)
All
piping
in
the
system
supplying
sprinklers
is
listed
and
conforms to the piping specifications of this
standard.
Piping connected to this
system and supplying plumbing
fixtures
only is required to comply with local plumbing and
health authority requirements but is
not required to be
listed.
(d)
Permitted by the local
plumbing or health authority.
(e)
A sign is affixed adjacent to the main
shut-off valve
that
states
in
minimum
1
/
4
-inch
letters,
“Warning,
the
water
system
for this home supplies a fire sprinkler system
that
depends on certain flows and
pressures being available to
fight a
fire. Devices
that restrict
the
flow or
decrease
the
pressure such as water softeners shall
not be added to this
system
without
a
review
of
the
fire
sprinkler
system
by
a
fire
protection specialist. Do not remove
this sign.”
2-4 Manufactured
Home Water Supply.
A water supply for a
sprinklered dwelling manufactured
off-
site shall not be less than that specified on the
manufacturer’s nameplate.
[See 4-4.3(k), Exception No.
2.
See Chapter 5 for an
alternative design approach for
manufactured homes.]
Chapter
3 System Components
3-1 Valves and
Drains.
3-1.1
Each
system
shall
have
a
single
control
valve
arranged
to
shut
off both the domestic system and the
sprinkler system, and
there shall be a
separate shutoff valve for the domestic
system only.
Exception No. 1: The sprinkler system
piping shall be
permitted to have a
separate control valve where supervised
by one of the following
methods:
(a) Central
station, proprietary, or remote station alarm
service
(b)
Local alarm service that causes the sounding of an
audible signal at a constantly attended
location.
(c) Valves that
are locked open
Exception
No. 2: A separate shutoff valve shall not be
required
for
the
domestic
water
supply
in
multipurpose
piping
systems.
3-1.2
Each
sprinkler system shall have a drain and/or test
connection with a valve on the system
side of the control
valve.
3-1.3
Additional
drains
shall
be
installed
for
each
trapped
portion
of a dry system that
is subject to freezing temperatures.
3-1.4*
Where
waterflow alarms are provided, inspector’s test
connections shall be installed at
locations that allow flow
testing
of
water
supplies,
connections,
and
alarm
mechanisms.
Where sprinklers
used in the system have a nominal K-factor
smaller than
5.6, the
inspector’s test
shall
be of
the same
size orifice as the smallest
sprinkler.
3-2 Pressure
Gauges.
A
pressure
gauge
shall
be
installed
to
indicate
air
pressure
on dry systems and
on water supply pressure tanks.
3-3
Piping.
3-3.1*
Pipe or tube used in sprinkler systems
shall be of the
materials
specified
in
Table
3-3.1
or
in
accordance
with
3-3.2
through
3-3.5.
The
chemical
properties,
physical
properties,
and dimensions
of the materials in Table 3-3.1 shall be at
least equivalent to the standards cited
in the table and
designed
to
withstand
a
working
pressure
of
not
less
than
175
psi
(12.1 bar).
Exception: When
multipurpose
piping
system
pressures
do
not
exceed
130
psi
(8.9
bar)
and
when
such
systems
are
not
equipped
with
a
fire
department
connection,
piping
shall
be
permitted
to be designed to
withstand a working pressure of not less
than 130 psi (8.9 bar). When
nonmetallic piping is used for
this
application, it shall be permitted to be rated at
not
less
than
130
psi
(8.9
bar)
working
pressure
at
not
less
than
120°F
(49°C).
3-3.2*
Other types of pipe or tube shall be
permitted to be used,
where
investigated and listed for sprinkler systems by a
testing and inspection agency
laboratory. Listed piping
materials
including, but not limited to, chlorinated
polyvinyl chloride (CPVC), polybutylene
(PB), and steel
differing from those
provided in Table 3-3.1 shall be
installed in accordance with their
listings and the
manufacturers’
installation
instructions.
CPVC
and PB pipe
and tube shall comply with the portions
of the American
Society
for
Testing
and
Materials
(ASTM)
standards
specified
in Table 3-3.2 that apply to fire
protection service in
addition to the
provisions of this paragraph.
Table 3-3.1 Pipe or Tube Materials and
Dimensions
Materials and
Dimensions
Standard
Specification for Black and Hot-Dipped
ASTM A 795
Zinc-Coated
(Galvanized) Welded and
Seamless Steel
Pipe for Fire Protection Use
Specification for Welded and Seamless
Pipe
ASTM A 53
Wrought Steel
Pipe
ANSI B36.10M
Specification for Electric-Resistance-
Welded
ASTM A 135
Steel Pipe
Specification for Seamless Copper Tube
ASTM B 75
[Copper Tube
(Drawn, Seamless)]
Specification for
Seamless Copper Water Tube
ASTM B 88
Specification for General Requirements
for
ASTM B 251
Wrought Seamless Copper and
Copper-Alloy
Tube
Fluxes for Soldering Applications of
Copper
ASTM B
813
and Copper-Alloy Tube
Specification for Filler Metals for
Brazing and
AWS A5.8
Braze
Welding (BCuP, copper- phosphorus, or
copper-phosphorus-silver
brazing filler metal)
Specification for Solder Metal [alloy
grades
ASTM B 32
containing less than 0.2 percent lead
as
identified in
ASTM B 32, Table 5,
Section
1,
and having a solidus temperature
that exceeds
400°
F (204°
C)]
Table 3-3.2 Specially
Listed Pipe or Tube Materials and
Dimensions
Materials and Dimensions
Standard
Nonmetallic Piping:
Specification for
Chlorinated Polyvinyl
ASTM F 442
Chloride (CPVC) Pipe
Specification for Polybutylene (PB)
Pipe
ASTM D 3309
Note: In
addition to satisfying these minimum standards,
specially listed pipe shall be required
to comply with the
provisions of 3-3.2.
3-3.2.1
When nonmetallic piping is installed in
attics, adequate
insulation
shall be provided
on the
attic
side of
the
piping
to
avoid
exposure of
the
piping to temperatures
in
excess
of
the pipe’s rated
temperature.
3-3.3
Wherever
the word
pipe
is used in
this standard, it shall be
understood
also to mean
tube
.
3-3.4
Schedule 10
steel pipe shall be permitted to be joined with
mechanical groove couplings approved
for service, with
grooves rolled on the
pipe by an approved groove-rolling
machine.
3-3.5
Fittings
used
in
sprinkler
systems
shall
be
of
the
materials
listed in Table 3-3.5 or in accordance
with 3-3.7. The
chemical
properties,
physical
properties, and
dimensions
of
the materials specified
in Table 3-3.5 shall be at least
equivalent
to
the
standards
cited
in
the
table.
Fittings
used
in
sprinkler
systems
shall
be
designed
to
withstand
a
working
pressure of not less
than 175 psi (12.1 bar).
Exception: When
multipurpose
piping
system
pressures
do
not
exceed
130
psi
(8.9
bar)
and
when
such
systems
are
not
equipped
with
a fire department connection, fittings shall be
permitted to be designed to withstand a
working pressure of
not less than 130
psi (8.9 bar). When nonmetallic fittings
are used for this application, they
shall be permitted to be
rated at not
less than 130 psi (8.9 bar) working pressure at
not less tha
n 120°F
(49°C).
Table 3-3.5 Fitting
Materials and Dimensions
Materials and Dimensions
Cast Iron:
Gray
Iron Threaded Fittings
Cast Iron Pipe
Flanges and Flanged Fittings
Malleable
Iron:
Malleable Iron
Threaded Fittings
Steel:
Factory-Made Wrought Steel
Buttweld Fittings
Buttwelding Ends
Specification for Piping Fittings of
Wrought
Carbon Steel and Alloy Steel
for Moderate
and Elevated Temperatures
Pipe Flanges and Flanged Fittings
Forged Fittings, Socket-Welding and
Threaded
Copper:
Wrought Copper and Copper Alloy
SolderJoint Pressure Fittings
Cast Copper Alloy Solder Joint Pressure
Fittings
Standard
ASME
B16.4
ASME B16.1
ASME B16.3
ASME B16.9
ASME B16.25
ASTM A 234
ASME B16.5
ASME B16.11
ASME
B16.22
ASME B16.18
3-3.6
Joints for
the connection of copper tube shall be
brazed.
Exception: Soldered
joints
shall
be
permitted
to
be
used
for
wet pipe
copper tube systems.
3-3.7*
Other
types of fittings shall be permitted to be used,
but
only where investigated and listed
for sprinkler systems by
a testing and
inspection agency laboratory. Listed fittings
including,
but
not
limited
to,
CPVC,
PB,
and
steel
differing
from those provided in Table 3-3.5
shall be installed in
accordance with
their listings and the manufacturers’
installation
instructions.
CPVC
and
PB
pipe
and
tube
fittings
shall
comply
with
the
portions
of
the
ASTM
standards
specified
in Table 3-3.7
that apply to fire protection service in
addition to the provisions of this
paragraph.
Table 3-3.7
Specially Listed Fittings and
Dimensions
Materials and
Dimensions
Standard
Specification for Schedule 80 CPVC
ASTM F 437
Threaded Fittings
Specification for Schedule 40 CPVC
ASTM F 438
Socket-Type
Fittings
Specification for Schedule 80
CPVC
ASTM F 439
Socket-Type
Fittings
Note: In addition to
satisfying these minimum standards,
specially listed pipe fittings shall be
required to comply
with the provisions
of 3-3.7.
3-4 Piping
Support.
3-4.1
Piping shall be supported from
structural members using
support
methods comparable to those required by local
plumbing codes.
Exception: Listed piping shall be
supported in accordance
with any
listing limitations.
3-4.2
Piping laid
on open joists or rafters shall be secured to
prevent lateral movement.
3-4.3*
Sprinkler
piping
shall
be
adequately
secured
to
restrict
the
movement of piping upon sprinkler
operation.
3-5 Sprinklers.
3-5.1
Listed
residential sprinklers shall be used. Listing
shall
be
based
on
tests to establish the ability
of the
sprinklers
to control residential fires
under standardized fire test
conditions. The standardized room fires
shall be based on a
residential array
of furnishings and finishes.
Exception No. 1: Residential
sprinklers shall not be used
in dry
pipe systems unless specifically listed for that
purpose.
Exception No. 2: Listed dry-type
sprinklers shall be
permitted to be
used in accordance with 4-3.2.
3-5.2 Temperature Ratings.
The
requirements
of
3-5.2.1
through
3-5.2.3
shall
be
used
for
the selection of
sprinkler temperature ratings.
3-5.2.1
Ordinary
temperature-rated
residential
sprinklers
[135°F
to
170°F
(57°C to 77°C)] shall be installed where maximum
ambient ceiling temperatures do not
exceed 100°F (38°C).
Table
3-5.2.3 Minimum Distances for Ordinary- and
Intermediate-Temperature Residential
Sprinklers
Minimum Distance from
Edge
of Source to
Ordinary-Temperature
Sprinkler
Heat Source
in.
mm
Side of
open or recessed fireplace
36
914
Front of recessed
fireplace
60
1524
Coal- or wood-burning stove
42
1067
Kitchen
range
18
457
Wall
oven
18
457
Hot
air flues
18
457
Uninsulated heat ducts
18
457
Uninsulated hot water
pipes
12
305
Side
of ceiling- or wall-mounted
24
607
hot air diffusers
Front of wall-mounted hot air
36
914
diffusers
Hot water heater or furnace
6
152
Light
fixture
Minimum
Distance from
Edge of Source to
Intermediate-Temperature
Sprinkler
in.
mm
12
305
36
914
12
305
9
229
9
229
9
229
9
229
6
152
12
305
18
3
457
76
0W-250W
250W-499W
6
12
152
305
3
6
76
152
3-5.2.2
Intermediate temperature-rated
residential sprinklers
[175°F
to
225°F
(79°C
to
107°C)]
shall
be
installed
where
maximum ambient ceiling temperatures
are between 101°F and
150°F (39°C and
66°C).
3-5.2.3
The following practices shall be
observed where installing
residential
sprinklers.
Exception:
Where higher expected ambient temperatures are
otherwise determined.
(1)
Sprinklers under glass
or plastic skylights exposed to
direct
rays of the sun shall be of
intermediate-temperature
classification.
(2)
Sprinklers in an unventilated concealed
space under an
uninsulated roof or in
an unventilated attic shall be of
intermediate-temperature
classification.
(3)
Sprinklers
installed
near
specific
heat
sources
that
are
identified in Table
3-5.2.3 shall be of ordinary- or
intermediate-temperature rating, as
indicated.
Exception: Where
sprinklers are listed for positioning
closer to a heat source than the
minimum distance shown in
Table
3-5.2.3, the closer minimum distances shall be
permitted to be used.
3-5.3
Operated or
damaged sprinklers shall be replaced with
sprinklers
having
the
same
performance
characteristics
as
the
original
equipment.
3-5.4 Painting
and Ornamental Finishes.
3-5.4.1*
Sprinkler
frames
shall
be
permitted
to
be
factory
painted
or
enameled as ornamental
finish in accordance with 3-5.4.2;
otherwise, sprinklers shall not be
painted, and any
sprinklers
that
have
been
painted
shall
be
replaced
with
new,
listed
sprinklers.
Exception:
Sprinklers painted with factory-applied
coatings shall not be required to be
replaced.
3-5.4.2
Ornamental
finishes
shall
not
be
applied
to
sprinklers
by
an
individual other than the sprinkler
manufacturer, and only
sprinklers
listed with such finishes shall be
used.
3-5.5 Escutcheon
Plates.
-
-
-
-
-
-
-
-
-
上一篇:消防行业专有名词中英对照
下一篇:高尔夫中英文常用语