关键词不能为空

当前您在: 主页 > 英语 >

NFPA标准系列

作者:高考题库网
来源:https://www.bjmy2z.cn/gaokao
2021-02-10 17:11
tags:

-

2021年2月10日发(作者:姜姓)


NFPA 13D


Standard for the Installation of Sprinkler


Systems


in


One-


and


Two-Family Dwellings


and


Manufactured Homes


1999 Edition


Copyright


?


1999 NFPA, All Rights Reserved


This edition of NFPA 13D,


Standard for the Installation of


Sprinkler Systems in One- and Two- Family Dwellings and


Manufactured Homes


, was prepared by the Technical Committee


on Residential Sprinkler Systems, released by the Technical


Correlating Committee on Automatic Sprinkler Systems, and


acted on by the National Fire Protection Association, Inc.,


at its May Meeting held May 17-20, 1999, in Baltimore, MD.


It


was


issued


by


the


Standards


Council


on


July


22,


1999,


with


an effective date of August 13, 1999, and supersedes all


previous editions.


Changes


other


than


editorial


are


indicated


by


a


vertical


rule


in the margin of the pages on which they appear. These lines


are


included


as


an


aid


to


the


user


in


identifying


changes


from


the previous edition.


This


edition


of


NFPA


13D


was


approved


as


an


American


National


Standard on August 13, 1999.


Origin and Development of NFPA 13D


Recognizing


the


need


to


reduce


the


annual


life


loss


from


fire


in residential occupancies (about 50 percent of total loss


of life by fire), the Committee on Automatic Sprinklers


appointed


a


subcommittee


in


May


1973


to


prepare


the


Standard


on the Installation of Sprinkler Systems in One- and


Two- Family Dwellings and Mobile Homes


. The subcommittee was


composed


of


members


of


the


Committee


on


Automatic


Sprinklers


and other technically competent experts. The standard was


submitted


and


adopted


at


the


NFPA


Annual


Meeting


in


Chicago,


IL, on May 12-16, 1975.


The 1980


edition


was a complete


rewrite of


the


1975 edition,


including SI units where appropriate. The 1980 edition


incorporated the results of the residential sprinkler test


program administered by the National Fire Protection


Association and funded by a research grant from the United


States Fire Administration. Factory Mutual Research


Corporation and the Los Angeles City Fire Department


conducted the dwelling tests. Factory Mutual Research


Corporation,


McNeary


Insurance Consulting Services, and


the


Charlotte, North Carolina, Fire Department conducted the


mobile home tests.


After gaining practical experience using the 1980 edition,


modifications to the standard, including removal of design


parameters for dry pipe systems, were made in the 1984


edition.


The 1989 and 1991 editions established criteria for the use


of antifreeze systems as well as some of the installation


criteria


associated with specially


listed


piping


materials.


The


1994


edition


provided


expanded


information


on


nonmetallic


pipe and introduced a new design option that reduced water


storage requirements for limited area dwellings.


The 1996 edition of the standard included expanded


information on the use and placement of residential


sprinklers


near


heat


sources.


For


the


first


time


since


1941,


the use of


1


/


2


-in. (12.7-mm) piping material was permitted


again for sprinkler systems under specific conditions. A


number


of


appendix


figures


were


also


added


to


address


methods


for protecting pipe from freezing in unheated attics.


The 1999 edition revises criteria for certain types of


multipurpose


piping


systems


and


adds


requirements


to


mitigate


the effect of water softeners and filters on system


performance.


Information


on


the


application


of


solvent


cement


for nonmetallic piping systems has been provided and the


exception


for


omitting


sprinkler


coverage


in


attics


and


crawl


spaces has been modified.


Technical Correlating Committee on Automatic Sprinkler


Systems (AUT-AAC)


John G. O’Neil


l,



Chair


Gage-Babcock & Assoc. Inc., VA [SE]


Milosh T. Puchovsky,



Nonvoting Secretary


Nat’l Fire Protection Assn., MA



Jose R. Baz,



Int’l Engineered Systems, LTD, Inc., FL [M]



Rep. NFPA Latin American Section


Kerry M. Bell,


Underwriters Laboratories Inc., IL [RT]


Eric H. Cote,


Rolf Jensen & Assoc., Inc., MA [SE]


Russell P. Fleming,



Nat’l Fire Sprinkler Assn., NY [M]



Joseph B. Hankins, Jr.,


Factory Mutual Research Corp., MA


[I]


Roland J. Huggins,


American Fire Sprinkler Assn., Inc., TX


[IM]


Sultan M. Javeri,



Protection Int’l, Ltd, France [I]



Andrew


Kim,



Nat’l


Research


Council


of


Canada,


ON,


Canada


[RT]



Gerald R. Kirby,



Marriott Int’l, Inc., DC [U]



Rep. American Hotel & Motel Assn.


B. J. Lukes,


Grinnell Fire Protection System Co. Ltd/Tyco,


Canada [M]


Rep. Canadian Automatic Sprinkler Assn.


Joseph W. Noble,


Clark County Fire Dept., NV [E]


Donald R. Oliver,


Wilson Fire/Rescue Services, NC [E]


Rep. Int’l Assn. of Fire Chiefs



James Retzloff,


The Viking Corp., MI [M]


Chester W. Schirmer,


Schirmer Engr Corp., NC [SE]


John Nigel Stephens,


Loss Prevention Council, England [I]


Lynn K. Underwood,


Wausau HPR Engr, WI [I]


John J. Walsh,


UA Joint Apprenticeship Committee Local 669,


MD [L]


Rep.


United


Assn.


of


Journeymen/Apprentices


of


Plumbing/Pipe


Fitting


Alternates


Donald


“Don” D. Becker,


Midland Automatic Sprinkler Co.,


Inc., MO [IM]


(Alt. to R. J. Huggins)


Raymond A. Grill,


Rolf Jensen & Assoc., Inc., VA [SE]


(Alt. to E. H. Cote)


Kenneth E. Isman,



Nat’l Fire Sprinkler Assn., NY [M]



(Alt. to R. P. Fleming)


George E. Laverick,


Underwriters Laboratories Inc., IL [RT]


(Alt. to K. M. Bell)


Donato


A.


Pirro


E.,



Electro


Sistemas


De


Panama,


S.A.,


Panama


[M]


(Alt. to J. R. Baz)


William E. Wilcox,


Factory Mutual Research Corp., MA [I]


(Alt. to J. B. Hankins, Jr.)


Nonvoting


Edward K. Budnick,


Hughes Assoc., Inc., MD [SE]


Rolf H. Jensen,


Belleair, FL [SE]


(Member Emeritus)


William E. Koffel, Jr.,


Koffel Assoc. Inc., MD [SE]


Kenneth W. Linder,


HSB Industrial Risk Insurers, CT [I]


Christopher T. Lummus,


Insurance Services Office, Inc., TX


[I]


Daniel Madrzykowski,



U.S. Nat’l Inst. of Standards &


Technology, MD [RT]


Peter Papavasiliou,


Engr Professionals, Ltd, IL [SE]


J. William Sheppard,


General Motors Corp., MI [U]


Milosh T. Puchovsky,


NFPA Staff Liaison


This


list


represents


the


membership


at


the


time


the


Committee


was


balloted


on


the


text


of


this


edition.


Since


that


time,


changes


in


the


membership


may


have


occurred. A


key to classifications is found


at


the


back of this document.


NOTE:


Membership


on


a


committee


shall


not


in


and


of


itself


constitute


an


endorsement


of


the


Association


or


any


document


developed


by


the


committee


on


which


the member serves.


Committee Scope:


The committee shall have overall


responsibility for documents that pertain to the


criteria for the design and installation of


automatic, open and foam-water sprinkler systems,


including the character and adequacy of water


supplies,


and


the


selection


of


sprinklers,


piping,


valves, and all materials and accessories. This


committee does not cover the installation of fire


pumps, nor the construction and installation of


gravity and pressure tanks and towers, nor the


installation, maintenance, and use of central


station, proprietary, auxiliary, and local


signaling systems for watchmen, fire alarm,


supervisory service, nor the design of fire


department hose connections.


Technical Committee on Residential Sprinkler Systems


(AUT-RSS)


Daniel Madrzykowski,



Chair


U.S. Nat’l Inst. of Standards & Technology, MD [RT]



George W. Baker,


Mashpee Fire & Rescue Dept., MA [E]


Rep. Int’l Assn. of Fire


Chiefs


Frederick J. Benn,


Advanced Automatic Sprinkler, Inc., CA


[IM]


Frederick C. Bradley,


Gage- Babcock & Assoc. Inc., GA [SE]


Lawrence Brown,



Nat’l Assn. of Home Builders, DC [U]



Edward K. Budnick,


Hughes Assoc., Inc., MD [SE]


Brian Hoening,


Globe Fire Sprinkler Corp., MI [M]


Rep. Nat’l Fire Sprinkler Assn.



Kenneth E. Isman,



Nat’l Fire Sprinkler Assn., NY [M]



Hsiang-Cheng Kung,


Factory Mutual Research Corp., MA [I]


George E. Laverick,


Underwriters Laboratories Inc., IL [RT]


Tom Lawrence,


Smith Fire Sprinkler Co., Inc., FL [IM]


Rep. American Fire Sprinkler Assn., Inc.


John C. Livingston, Jr.,


Livingston Fire Protection, Inc.,


MD [IM]


Rep. Nat’l Fire Sprinkler Assn.



Raymond H. Lower,


Cigna Loss Control Services, WA [I]


Rep. American Insurance Services Group, Inc.


M.


L.


“Larry”


Maruskin,



Federal


Emergency


Mgmt.


Agency,


MD


[C]


Michael Nelson,


Rolf Jensen & Assoc., Inc., NY [SE]


Ronald G. Nickson,



Nat’l Multi Housing Council, DC [U]



Maurice M. Pilette,


Mechanical Designs Ltd., MA [SE]


Chester W. Schirmer,


Schirmer Engr Corp., NC [SE]


Sandra Stanek,


Rural Metro Fire Dept., AZ [E]


Donald Townley,


B. F. Goodrich, OH [M]


Rep. Committee for Firesafe Dwellings


John J. Walsh,


UA Joint Apprenticeship Committee Local 669,


MD [L]


Rep.


United


Assn.


of


Journeymen/Apprentices


of


Plumbing/Pipe


Fitting


Susan J. Weigand,


Victory Fire Protection, Inc., PA [IM]


Rep. American Fire Sprinkler Assn., Inc.


Alternates


Carl F. Baldassarra,


Schirmer Engr Corp., IL [SE]


(Alt. to C. W. Schirmer)


Phillip


A.


Brown,



American


Fire


Sprinkler


Assn.,


Inc.,


TX


[IM]


(Alt. to S. J. Weigand)


William M. Carey,


Underwriters Laboratories Inc., IL [RT]


(Alt. to G. E. Laverick)


Thomas Deegan,


Viking Corp., MI [M]


(Alt. to B. Hoening)


Gary L. Johnson,


B. F. Goodrich, OH [M]


(Alt. to D. Townley)


John C. McDonald,


Virginia Sprinkler Co., Inc., VA [IM]


(Alt. to T. Lawrence)


Michael


A.


Rothmier,



UA


Joint


Apprenticeship


Committee


Local


669, MD [L]


(Alt. to J. J. Walsh)


Harry Shaw,


Harry Shaw & Assoc. Inc., MD [E]


(Alt. to G. W. Baker)


George Stanley,


Wiginton Fire Sprinklers, FL [IM]


(Alt. to J. C. Livingston, Jr.)


David


W.


Stroup,



U.S.


Nat’l


Inst.


of


Standards


&


Technology,


MD [RT]


(Alt. to D. Madrzykowski)


Richard


E.


Thonnings,



American


Insurance


Services


Group,


Inc.,


NY [I]


(Alt. to R. H. Lower)


Randolph W. Tucker,


Rolf Jensen & Assoc., Inc., TX [SE]


(Alt. to M. Nelson)


Terry L. Victor,



Tyco Int’l, Ltd, MD [M]



(Alt. to K. E. Isman)


Bennie Vincent,


Factory Mutual Research Corp., MA [I]


(Alt. to H. Kung)


Joseph Wiehagen,



Nat’l Assn. of Home Builders, MD [U]



(Alt. to L. Brown)


Nonvoting


Rohit


Khanna,



U.S.


Consumer


Product


Safety


Commission,


MD


[C]


Milosh T. Puchovsky,


NFPA Staff Liaison


This


list


represents


the


membership


at


the


time


the


Committee


was


balloted


on


the


text


of


this


edition.


Since


that


time,


changes


in


the


membership


may


have


occurred. A


key to classifications is found


at


the


back of this document.


NOTE:


Membership


on


a


committee


shall


not


in


and


of


itself


constitute


an


endorsement


of


the


Association


or


any


document


developed


by


the


committee


on


which


the member serves.


Committee Scope:


The committee shall have primary


responsibility for documents on the design and


installation of automatic sprinkler systems in


dwellings and residential occupancies up to and


including four stories in height, including the


character and adequacy of water supplies, and the


selection of sprinklers, piping, valves and all


materials and accessories.


NFPA 13D


Standard for the


Installation of Sprinkler Systems in One- and Two-Family


Dwellings and Manufactured Homes


1999 Edition



NOTICE: An asterisk (*) following the number or letter


designating a paragraph indicates that explanatory


material on the paragraph can be found in Appendix A.


Information on referenced publications can be found in


Chapter 6 and Appendix B.


Preface


It is intended that this standard provide a method for


those individuals wishing to install a sprinkler system


for


additional


life


safety


and


property


protection.


It


is


not the purpose of this standard to require the


installation of an automatic sprinkler system. This


standard


assumes


that


one


or


more


smoke


detectors


will


be


installed


in


accordance


with


NFPA


72,



National


Fire


Alarm


Code


?


.


Chapter 1 General Information


1-1* Scope.


This


standard


covers


the


design


and


installation


of


automatic


sprinkler


systems


for


protection


against


the


fire


hazards


in


one- and two-family dwellings and manufactured homes.


1-2* Purpose.


The


purpose


of


this


standard


is


to


provide


a


sprinkler


system


that aids in the detection and control of residential fires


and thus provides improved protection against injury, life


loss, and property damage. A sprinkler system designed and


installed in accordance with this standard is expected to


prevent flashover (total involvement) in the room of fire


origin, where sprinklered, and to improve the chance for


occupants to escape or be evacuated.


Guidelines have been established for the design and


installation of sprinkler systems for one- and two-family


dwellings and manufactured homes. Nothing in this standard


is intended to restrict new technologies or alternative


arrangements, provided that the level of safety prescribed


by the standard is not reduced.


1-3 Definitions.


Approved.*


Acceptable to


the authority having


jurisdiction.


Authority


Having


Jurisdiction.*



The


organization,


office,


or


individual responsible for approving equipment, materials,


an installation, or a procedure.


Check Valve.



A valve


that allows


flow


in one direction


only.


Control Valve.*


A valve employed to control (shut) a supply


of water to a sprinkler system.


Design


Discharge.



The


rate


of


water


discharged


by


an


automatic


sprinkler expressed in gpm (L/min).


Dry


System.



A


system


employing


automatic


sprinklers


attached


to


a


piping


system


containing


air


under


atmospheric


or


higher


pressures. Loss of pressure from the opening of a sprinkler


or


detection


of a fire condition causes the release of


water


into the piping system and out the opened sprinkler.


Dwelling.



Any


building


that


contains


not


more


than


one


or


two


dwelling units intended to be used, rented, leased, let, or


hired out to


be occupied or


that are


occupied for habitation


purposes.


Dwelling


Unit.



One


or


more


rooms,


arranged


for


the


use


of


one


or more individuals living together, as in a single


housekeeping unit, that normally have cooking, living,


sanitary, and sleeping facilities.


Labeled.


Equipment or materials to which has been attached


a


label,


symbol,


or


other


identifying


mark


of


an


organization


that is acceptable to the authority having jurisdiction and


concerned with product evaluation, that maintains periodic


inspection of production of labeled equipment or materials,


and by whose labeling the manufacturer indicates compliance


with appropriate standards or performance in a specified


manner.


Listed.*



Equipment,


materials,


or


services


included


in


a


list


published by an organization that is acceptable to the


authority having jurisdiction


and concerned


with


evaluation


of products or services, that maintains periodic inspection


of production of listed equipment or materials or periodic


evaluation


of


services,


and


whose


listing


states


that


either


the equipment, material, or service meets appropriate


designated standards or has been tested and found suitable


for a specified purpose.


Manufactured


Home.*



A


structure,


transportable


in


one


or


more


sections, that in the traveling mode is 8 body ft (2.4 m) or


more


in


width


and


40


body


ft


(12


m)


or


more


in


length


or,


where


erected


on-site,


is


320


ft


2



(28


m


2


)


or


more,


and


that


is


built


on a permanent chassis and designed to be used as a dwelling


with


or


without


a


permanent


foundation


where


connected


to


the


required utilities, and includes the plumbing, heating, air


conditioning, and electrical systems contained therein.


Multipurpose


Piping


System.



A


piping


system


within


dwellings


and manufactured homes intended to serve both domestic and


fire protection needs.


Preengineered


System.



A


packaged


sprinkler system including


all


components


connected


to


the


water


supply


and


designed


to


be installed according to pretested limitations.


Pump.


A mechanical device that transfers or raises, or


transfers and raises, the pressure of a fluid (water).


Residential Sprinkler.


A type of sprinkler that meets the


definition of fast response as defined by NFPA 13,


Standard


for


the


Installation


of


Sprinkler


Systems


,


and


that


has


been


specifically investigated for its ability to enhance


survivability in the room of fire origin and that is listed


for use in the protection of dwelling units.


Shall.


Indicates a mandatory requirement.


Should.


Indicates a recommendation or that which is advised


but not required.


Sprinkler, Automatic.


A fire suppression or control device


that operates automatically when its heat-actuated element


is heated to its thermal rating or above, allowing water to


discharge over a specific area.


Sprinkler System.


An integrated system of piping, connected


to


a


water


supply,


with


listed


sprinklers


that


automatically


initiate water discharge over a fire area. Where required,


the sprinkler system also includes a control valve and a


device for actuating an alarm when the system operates.


Standard.


A document, the main text of which contains only


mandatory provisions using the word “shall” to indicate


requirements and which is in a form generally suitable for


mandatory reference by another standard or code or for


adoption into law. Nonmandatory provisions shall be located


in an appendix, footnote, or fine-print note and are not to


be considered a part of the requirements of a standard.


Supply Pressure.


The pressure within the supply (e.g., city


or private supply water source).


System


Pressure.



The


pressure


within


the


system


(e.g.,


above


the control valve).


System Working Pressure.


The maximum anticipated static


(nonflowing)


or


flowing


pressure


applied


to


sprinkler


system


components exclusive of surge pressures.


Waterflow Alarm.


A sounding device activated by a waterflow


detector


or alarm check valve and arranged to


sound an


alarm


that is audible in all living areas over background noise


levels with all intervening doors closed.


Waterflow


Detector.



An


electric


signaling


indicator


or


alarm


check valve actuated by waterflow in one direction only.


Wet


System.



A


system


employing


automatic


sprinklers


that


are


attached to a piping system containing water and connected


to a water supply so that water discharges immediately from


sprinklers opened by a fire.


1-4* Maintenance.


The owner is responsible for the condition of a sprinkler


system and shall keep the system in normal operating


condition.


1-5 Devices, Materials, Design, and Installation.


1-5.1*



Only new residential sprinklers shall be employed in the


installation of sprinkler systems.



1-5.2



Only


listed


and


approved


devices


and


approved


materials


shall


be used in sprinkler systems.



Exception: Listing


shall


be


permitted


to


be


waived


for


tanks,


pumps, hangers, waterflow detection devices, and waterflow


valves.



1-5.3



Where


listed,


preengineered


systems


shall


be


installed


within


the limitations that have been established by the testing


laboratories.



1-5.4*



All systems shall be tested for leakage at normal system


operating water pressure.



Exception: Where a fire department pumper connection is


provided, hydrostatic pressure tests shall be provided in


accordance with NFPA 13, Standard for the Installation of


Sprinkler Systems.



1-5.5



Where


solvent


cement


is


used


as


the


pipe


and


fittings


bonding


agent,


sprinklers


shall


not


be


installed


in


the


fittings


prior


to the fittings being cemented in place.



1-6* Units.


Metric units of measurement in this standard shall be in


accordance with the modernized metric system known as the


International System of Units (SI). The liter and bar units


are outside of, but recognized by, SI and are commonly used


in international fire protection. These units are provided


in Table 1-6 with their conversion factors.


Table 1-6 Metric Conversions



Name of Unit


liter


pascal


bar


bar



Unit Symbol











L











Pa











bar











bar


Conversion Factor








1 gal = 3.785 L








1 psi = 6894.757 Pa








1 psi = 0.0689 bar







1 bar = 105 Pa


1-6.1



Where a value for measurement as specified in this standard


is


followed by


an equivalent value in


other


units, the


first


stated value shall be regarded as the requirement. A given


equivalent value shall be considered to be approximate.



1-6.2



SI units have been converted by multiplying the quantity by


the conversion factor and then rounding the result to the


appropriate number of significant digits.



Chapter 2 Water Supply


2-1 General Provisions.


Every automatic sprinkler system shall have at least one


automatic


water


supply.


Where


stored


water


is


used


as


the


sole


source


of


supply,


the


minimum


quantity


shall equal


the


water


demand rate times 10 minutes.


(See 4-1.3.)


Exception: For dwelling units that are one story in height


and


less


than


2000


ft


2



(186


m


2


)


in


area,


the


water


supply


shall


be at least 7 minutes for the two-sprinkler demand.


2-2* Water Supply Sources.


The


following


water


supply


sources


shall


be


considered


to


be


acceptable by this standard:


(1)


A connection to a reliable waterworks system with or


without an automatically operated pump


(2)


An elevated tank


(3)


A


pressure


tank


designed


to


American


Society


of


Mechanical


Engineers (ASME) standards for a pressure vessel with a


reliable pressure source


(4)


A


stored


water


source


with


an


automatically


operated


pump


2-3* Multipurpose Piping System.


A piping system serving both sprinkler and domestic needs


shall be considered to be acceptable by this standard where


the following conditions are met.


(a)


*


In


common


water


supply


connections


serving


more


than


one


dwelling


unit,


5


gpm


(19


L/min)


are


added


to


the


sprinkler


system


demand to


determine the size


of common


piping


and


the


size of the total water supply requirements.


Exception: Domestic design demand shall not be required to


be added where provision is made to prevent flow into the


domestic water system upon operation of a sprinkler.


(b)


Smoke detectors are provided in accordance with NFPA


72,


National Fire Alarm Code


?


.


(c)


All


piping


in


the


system


supplying


sprinklers


is


listed


and conforms to the piping specifications of this standard.


Piping connected to this system and supplying plumbing


fixtures only is required to comply with local plumbing and


health authority requirements but is not required to be


listed.


(d)


Permitted by the local plumbing or health authority.


(e)


A sign is affixed adjacent to the main shut-off valve


that


states


in


minimum


1

< p>
/


4


-inch


letters,


“Warning,


the


water


system for this home supplies a fire sprinkler system that


depends on certain flows and pressures being available to


fight a fire. Devices


that restrict


the


flow or


decrease


the


pressure such as water softeners shall not be added to this


system


without


a


review


of


the


fire


sprinkler


system


by


a


fire


protection specialist. Do not remove this sign.”



2-4 Manufactured Home Water Supply.


A water supply for a sprinklered dwelling manufactured


off- site shall not be less than that specified on the


manufacturer’s nameplate.


[See 4-4.3(k), Exception No. 2.



See Chapter 5 for an alternative design approach for


manufactured homes.]


Chapter 3 System Components


3-1 Valves and Drains.


3-1.1



Each


system


shall


have


a


single


control


valve


arranged


to


shut


off both the domestic system and the sprinkler system, and


there shall be a separate shutoff valve for the domestic


system only.



Exception No. 1: The sprinkler system piping shall be


permitted to have a separate control valve where supervised


by one of the following methods:



(a) Central station, proprietary, or remote station alarm


service



(b) Local alarm service that causes the sounding of an


audible signal at a constantly attended location.



(c) Valves that are locked open



Exception No. 2: A separate shutoff valve shall not be


required


for


the


domestic


water


supply


in


multipurpose


piping


systems.



3-1.2



Each sprinkler system shall have a drain and/or test


connection with a valve on the system side of the control


valve.



3-1.3



Additional


drains


shall


be


installed


for


each


trapped


portion


of a dry system that is subject to freezing temperatures.



3-1.4*



Where waterflow alarms are provided, inspector’s test


connections shall be installed at locations that allow flow


testing


of


water


supplies,


connections,


and


alarm


mechanisms.


Where sprinklers used in the system have a nominal K-factor


smaller than


5.6, the inspector’s test


shall


be of the same


size orifice as the smallest sprinkler.



3-2 Pressure Gauges.


A


pressure


gauge


shall


be


installed


to


indicate


air


pressure


on dry systems and on water supply pressure tanks.


3-3 Piping.


3-3.1*



Pipe or tube used in sprinkler systems shall be of the


materials


specified


in


Table


3-3.1


or


in


accordance


with


3-3.2


through


3-3.5.


The


chemical


properties,


physical


properties,


and dimensions of the materials in Table 3-3.1 shall be at


least equivalent to the standards cited in the table and


designed


to


withstand


a


working


pressure


of


not


less


than


175


psi (12.1 bar).



Exception: When


multipurpose


piping


system


pressures


do


not


exceed


130


psi


(8.9


bar)


and


when


such


systems


are


not


equipped


with


a


fire


department


connection,


piping


shall


be


permitted


to be designed to withstand a working pressure of not less


than 130 psi (8.9 bar). When nonmetallic piping is used for


this application, it shall be permitted to be rated at not


less


than


130


psi


(8.9


bar)


working


pressure


at


not


less


than


120°F (49°C).



3-3.2*



Other types of pipe or tube shall be permitted to be used,


where investigated and listed for sprinkler systems by a


testing and inspection agency laboratory. Listed piping


materials including, but not limited to, chlorinated


polyvinyl chloride (CPVC), polybutylene (PB), and steel


differing from those provided in Table 3-3.1 shall be


installed in accordance with their listings and the


manufacturers’


installation


instructions.


CPVC


and PB pipe


and tube shall comply with the portions of the American


Society


for


Testing


and


Materials


(ASTM)


standards


specified


in Table 3-3.2 that apply to fire protection service in


addition to the provisions of this paragraph.



Table 3-3.1 Pipe or Tube Materials and Dimensions



Materials and Dimensions


Standard


Specification for Black and Hot-Dipped


ASTM A 795


Zinc-Coated (Galvanized) Welded and


Seamless Steel Pipe for Fire Protection Use


Specification for Welded and Seamless Pipe


ASTM A 53


Wrought Steel Pipe


ANSI B36.10M


Specification for Electric-Resistance- Welded


ASTM A 135


Steel Pipe


Specification for Seamless Copper Tube


ASTM B 75


[Copper Tube (Drawn, Seamless)]


Specification for Seamless Copper Water Tube


ASTM B 88


Specification for General Requirements



for


ASTM B 251


Wrought Seamless Copper and



Copper-Alloy


Tube


Fluxes for Soldering Applications of



Copper


ASTM B 813


and Copper-Alloy Tube



Specification for Filler Metals for Brazing and


AWS A5.8


Braze Welding (BCuP, copper- phosphorus, or


copper-phosphorus-silver



brazing filler metal)


Specification for Solder Metal [alloy



grades


ASTM B 32


containing less than 0.2 percent lead



as


identified in ASTM B 32, Table 5,



Section 1,


and having a solidus temperature



that exceeds


400°


F (204°


C)]



Table 3-3.2 Specially Listed Pipe or Tube Materials and


Dimensions



Materials and Dimensions


Standard


Nonmetallic Piping:



Specification for Chlorinated Polyvinyl


ASTM F 442


Chloride (CPVC) Pipe


Specification for Polybutylene (PB) Pipe


ASTM D 3309


Note: In addition to satisfying these minimum standards,


specially listed pipe shall be required to comply with the


provisions of 3-3.2.



3-3.2.1



When nonmetallic piping is installed in attics, adequate


insulation


shall be provided


on the


attic


side of


the piping


to


avoid


exposure of


the


piping to temperatures


in excess


of


the pipe’s rated temperature.



3-3.3



Wherever the word


pipe


is used in this standard, it shall be


understood also to mean


tube


.



3-3.4



Schedule 10 steel pipe shall be permitted to be joined with


mechanical groove couplings approved for service, with


grooves rolled on the pipe by an approved groove-rolling


machine.



3-3.5



Fittings


used


in


sprinkler


systems


shall


be


of


the


materials


listed in Table 3-3.5 or in accordance with 3-3.7. The


chemical


properties,


physical


properties, and


dimensions


of


the materials specified in Table 3-3.5 shall be at least


equivalent


to


the


standards


cited


in


the


table.


Fittings


used


in


sprinkler


systems


shall


be


designed


to


withstand


a


working


pressure of not less than 175 psi (12.1 bar).



Exception: When


multipurpose


piping


system


pressures


do


not


exceed


130


psi


(8.9


bar)


and


when


such


systems


are


not


equipped


with a fire department connection, fittings shall be


permitted to be designed to withstand a working pressure of


not less than 130 psi (8.9 bar). When nonmetallic fittings


are used for this application, they shall be permitted to be


rated at not less than 130 psi (8.9 bar) working pressure at


not less tha


n 120°F (49°C).



Table 3-3.5 Fitting Materials and Dimensions



Materials and Dimensions


Cast Iron:



Gray Iron Threaded Fittings


Cast Iron Pipe Flanges and Flanged Fittings


Malleable Iron:



Malleable Iron Threaded Fittings


Steel:



Factory-Made Wrought Steel


Buttweld Fittings


Buttwelding Ends


Specification for Piping Fittings of Wrought


Carbon Steel and Alloy Steel for Moderate


and Elevated Temperatures


Pipe Flanges and Flanged Fittings


Forged Fittings, Socket-Welding and


Threaded


Copper:



Wrought Copper and Copper Alloy


SolderJoint Pressure Fittings


Cast Copper Alloy Solder Joint Pressure


Fittings



Standard



ASME B16.4


ASME B16.1



ASME B16.3




ASME B16.9


ASME B16.25


ASTM A 234


ASME B16.5


ASME B16.11



ASME B16.22


ASME B16.18


3-3.6



Joints for the connection of copper tube shall be brazed.



Exception: Soldered


joints


shall


be


permitted


to


be


used


for


wet pipe copper tube systems.



3-3.7*



Other types of fittings shall be permitted to be used, but


only where investigated and listed for sprinkler systems by


a testing and inspection agency laboratory. Listed fittings


including,


but


not


limited


to,


CPVC,


PB,


and


steel


differing


from those provided in Table 3-3.5 shall be installed in


accordance with their listings and the manufacturers’


installation


instructions.


CPVC


and


PB


pipe


and


tube


fittings


shall


comply


with


the


portions


of


the


ASTM


standards


specified


in Table 3-3.7 that apply to fire protection service in


addition to the provisions of this paragraph.



Table 3-3.7 Specially Listed Fittings and Dimensions



Materials and Dimensions


Standard


Specification for Schedule 80 CPVC


ASTM F 437


Threaded Fittings


Specification for Schedule 40 CPVC


ASTM F 438


Socket-Type Fittings


Specification for Schedule 80 CPVC





ASTM F 439


Socket-Type Fittings


Note: In addition to satisfying these minimum standards,


specially listed pipe fittings shall be required to comply


with the provisions of 3-3.7.



3-4 Piping Support.


3-4.1



Piping shall be supported from structural members using


support methods comparable to those required by local


plumbing codes.



Exception: Listed piping shall be supported in accordance


with any listing limitations.



3-4.2



Piping laid on open joists or rafters shall be secured to


prevent lateral movement.



3-4.3*



Sprinkler


piping


shall


be


adequately


secured


to


restrict


the


movement of piping upon sprinkler operation.



3-5 Sprinklers.


3-5.1



Listed residential sprinklers shall be used. Listing shall


be


based


on tests to establish the ability


of the sprinklers


to control residential fires under standardized fire test


conditions. The standardized room fires shall be based on a


residential array of furnishings and finishes.



Exception No. 1: Residential sprinklers shall not be used


in dry pipe systems unless specifically listed for that


purpose.



Exception No. 2: Listed dry-type sprinklers shall be


permitted to be used in accordance with 4-3.2.



3-5.2 Temperature Ratings.



The


requirements


of


3-5.2.1


through


3-5.2.3


shall


be


used


for


the selection of sprinkler temperature ratings.



3-5.2.1



Ordinary


temperature-rated


residential


sprinklers


[135°F


to


170°F (57°C to 77°C)] shall be installed where maximum


ambient ceiling temperatures do not exceed 100°F (38°C).



Table 3-5.2.3 Minimum Distances for Ordinary- and


Intermediate-Temperature Residential Sprinklers




Minimum Distance from


Edge of Source to


Ordinary-Temperature


Sprinkler


Heat Source


in.


mm


Side of open or recessed fireplace


36


914


Front of recessed fireplace


60


1524


Coal- or wood-burning stove


42


1067


Kitchen range


18


457


Wall oven


18


457


Hot air flues


18


457


Uninsulated heat ducts


18


457


Uninsulated hot water pipes


12


305


Side of ceiling- or wall-mounted


24


607


hot air diffusers


Front of wall-mounted hot air


36


914


diffusers


Hot water heater or furnace


6


152


Light fixture




Minimum Distance from


Edge of Source to


Intermediate-Temperature


Sprinkler


in.


mm


12


305


36


914


12


305


9


229


9


229


9


229


9


229


6


152


12


305


18


3



457


76



0W-250W


250W-499W



6


12


152


305


3


6


76


152


3-5.2.2



Intermediate temperature-rated residential sprinklers


[175°F


to


225°F


(79°C



to


107°C)]


shall


be


installed


where


maximum ambient ceiling temperatures are between 101°F and


150°F (39°C and 66°C).



3-5.2.3



The following practices shall be observed where installing


residential sprinklers.



Exception: Where higher expected ambient temperatures are


otherwise determined.



(1)


Sprinklers under glass or plastic skylights exposed to


direct rays of the sun shall be of


intermediate-temperature classification.



(2)


Sprinklers in an unventilated concealed space under an


uninsulated roof or in an unventilated attic shall be of


intermediate-temperature classification.



(3)


Sprinklers


installed


near


specific


heat


sources


that


are


identified in Table 3-5.2.3 shall be of ordinary- or


intermediate-temperature rating, as indicated.



Exception: Where sprinklers are listed for positioning


closer to a heat source than the minimum distance shown in


Table 3-5.2.3, the closer minimum distances shall be


permitted to be used.



3-5.3



Operated or damaged sprinklers shall be replaced with


sprinklers


having


the


same


performance


characteristics


as


the


original equipment.



3-5.4 Painting and Ornamental Finishes.



3-5.4.1*



Sprinkler


frames


shall


be


permitted


to


be


factory


painted


or


enameled as ornamental finish in accordance with 3-5.4.2;


otherwise, sprinklers shall not be painted, and any


sprinklers


that


have


been


painted


shall


be


replaced


with


new,


listed sprinklers.



Exception: Sprinklers painted with factory-applied


coatings shall not be required to be replaced.



3-5.4.2



Ornamental


finishes


shall


not


be


applied


to


sprinklers


by


an


individual other than the sprinkler manufacturer, and only


sprinklers listed with such finishes shall be used.



3-5.5 Escutcheon Plates.


-


-


-


-


-


-


-


-



本文更新与2021-02-10 17:11,由作者提供,不代表本网站立场,转载请注明出处:https://www.bjmy2z.cn/gaokao/630384.html

NFPA标准系列的相关文章

  • 爱心与尊严的高中作文题库

    1.关于爱心和尊严的作文八百字 我们不必怀疑富翁的捐助,毕竟普施爱心,善莫大焉,它是一 种美;我们也不必指责苛求受捐者的冷漠的拒绝,因为人总是有尊 严的,这也是一种美。

    小学作文
  • 爱心与尊严高中作文题库

    1.关于爱心和尊严的作文八百字 我们不必怀疑富翁的捐助,毕竟普施爱心,善莫大焉,它是一 种美;我们也不必指责苛求受捐者的冷漠的拒绝,因为人总是有尊 严的,这也是一种美。

    小学作文
  • 爱心与尊重的作文题库

    1.作文关爱与尊重议论文 如果说没有爱就没有教育的话,那么离开了尊重同样也谈不上教育。 因为每一位孩子都渴望得到他人的尊重,尤其是教师的尊重。可是在现实生活中,不时会有

    小学作文
  • 爱心责任100字作文题库

    1.有关爱心,坚持,责任的作文题库各三个 一则150字左右 (要事例) “胜不骄,败不馁”这句话我常听外婆说起。 这句名言的意思是说胜利了抄不骄傲,失败了不气馁。我真正体会到它

    小学作文
  • 爱心责任心的作文题库

    1.有关爱心,坚持,责任的作文题库各三个 一则150字左右 (要事例) “胜不骄,败不馁”这句话我常听外婆说起。 这句名言的意思是说胜利了抄不骄傲,失败了不气馁。我真正体会到它

    小学作文
  • 爱心责任作文题库

    1.有关爱心,坚持,责任的作文题库各三个 一则150字左右 (要事例) “胜不骄,败不馁”这句话我常听外婆说起。 这句名言的意思是说胜利了抄不骄傲,失败了不气馁。我真正体会到它

    小学作文