itz-fgr
Fundamentals of protection
practice
The purpose of an electrical
power system is to generate and supply electrical
energy to consumers. The system should
be designed and managed to deliver this energy
to the utilization points with both
reliability and economy. As these two requirements
are
largely opposed, it is instructive
to look at the reliability of a system and its
cost and
value to the consumer.
One hand ,The diagram mast make sure
the reliability in system design,. On the
other hand, high reliability should not
be pursued as an end in itself, regardless of
cost,
but should rather be balanced
against economy,taking.
Security of
supply can be bettered by improving plant design,
increasing the spare
capacity margin
and arranging alternative circuits to supply
loads. Sub-division of the
system into
zones. each controlled by switchgear in
association with protective gear.
provides flexibility during normal
operation and ensures a minimum of dislocation
following a breakdown.
The
greatest threat to the security of a supply system
is the short circuit,which
imposes a
sudden and sometimes violent change on system
operation. The large current
which then
flows, accompanied by the localized release of a
considerable quantity of
energy, can
cause fire at the fault location, and mechanical
damage throughout the system,
particularly to machine and transformer
windings. Rapid isolation of the fault by the
nearest switchgear will minimize the
damage and disruption caused to the system.
A power system represents a very large
capital investment. To maximize the return
on this outlay. the system must be
loaded as much as possible. For this reason it is
necessary not only to provide a supply
of energy which is attractive to prospective users
by operating the system ,but also to
keep the system in full operation as far as
possible
continuously, so that it may
give the best service to the consumer, and earn
the most
revenue for the supply
authority. Absolute freedom from failure of the
plant and system
network cannot be guaran- teed. The
risk of a fault occurring, however slight for each
item, is multiplied by the number of
such items which are closely associated in an
extensive system, as any fault produces
repercussions throughout the network. When the
system is large, the chance of a fault
occurring and the disturbance that a fault would
bring are both so great that without
equipment to remove faults the system
will become, in practical terms, inoperable.
The object of the system will be
defeated if adequate provision for fault clearance
is not
made. Nor is the installation of
switchgear alone sufficient; discriminative
protective gear,
designed according to
the characteristics and requirements of the power
system. must be
provided to control the
switchgear. A system is not properly designed and
managed if it is
not adequately
protected.
Protective gear
This is a collective term which covers
all the equipment used for detecting,locating
and initiating the removal of a fault
from the power system. Relays are extensively used
for major protective functions, but the
term also covers direct-acting and fuses.
In addition to relays the term includes
all accessories such as current and voltage
transformers, shunts, a.c. wiring and
any other devices relating to the protective
relays.
In general, the main
switchgear, although fundamentally protective in
its function, is
excluded from the term
protective gear, as are also common services, such
as the station
battery and any other
equipment required to secure opera- tion of the
circuit breaker.
Reliablity
The performance of the protection
applied to large power systems is frequently
assessed numerically. For this purpose
each system fault is classed as an incident and
those which are cleared by the tripping
of the correct circuit breakers and only those,
are
classed as 'correct'. The
percentage of correct clearances can then be
determined.
This principle of assessment gives an
accurate evaluation of the protection of the
system as a whole, but it is severe in
its judgement of relay performance, in that many
relays are called into operation for
each system fault, and all must behave correctly
for a
correct clearance to be recorded.
On this basis, a performance of 94% is obtainable
by
standard techniques.
Complete reliability is unlikely ever
to be achieved by further improvements in
construction. A very big step, however,
can be taken by providing duplication of
equipment or 'redundancy'. Two complete
sets of equipment are provided, and arranged
so that either by itself can carry out
the required function. If the risk of an equipment
failing is x/unit. the resultant risk,
allowing for redundancy, is x2. Where x is small
the
resultant risk (x2 may
be negligible.
It has long
been the practice to apply duplicate protective
systems to busbars, both
being required
to operate to complete a tripping operation, that
is, a 'two-out-of-two'
arrangement. In
other cases, important circuits have been provided
with duplicate main
protection schemes,
either being able to trip independently, that is,
a 'one-out-of- two'
arrangement. The
former arrangement guards against unwanted
operation, the latter
against failure
to operate.
These two features can be
obtained together by adopting a 'two-out-of-three'
arrangement in which three basic
systems are used and are interconnected so that
the
operation of any two will complete
the tripping function. Such schemes have already
been used to a limited extent and
application of the principle will undoubtedly
increase.
Probability theory suggests
that if a power network were protected throughout
on this
basis, a protection performance
of 99.98% should be attainable. This performance
figure
requires that the separate
protection systems be completely independent; any
common
factors,
such as common current transformers or tripping
batteries, will reduce the overall
performance. SELECTIVITY
Protection is arranged in zones, which
should cover the power system completely,
leaving no part unprotected. When a
fault occurs the protection is required to select
and
trip only the neareat circuit
breakers. This property of selective tripping is
also called
'discrimination' and is
achieved by two general methods:
a Time
graded systems
Protective systems in
successive zones are arranged to operate in times
which are
graded through the sequence
of equipments so that upon the occurrence of a
fault,
although a number of protective
equipments respond, only those relevant to the
faulty
zone complete the tripping
functiopn. The others make incomplete operations
and then
reset.
b Unit
systems
It is possible to design
protective systems which respond only to fault
conditions
lying within a clearly
defined zone. This 'unit protection' or
'restricted protection' can be
applied
throughout a power system and, since it does not
involve time grading, can be
relatively
fast in operation.
Unit protection is
usually achieved by means of a comparison of
quantities at the
boundaries of the
zone. Certain protective systems derive their
'restricted' property
from the
configuration of the power system and may also be
classed as unit protection.
Whichever
method is used, it must be kept in mind that
selectivity is not merely a matter
of
relay design. It also depends on the correct co-
ordination of current transformers and
relays with a suitable choice of relay
settings, taking into account the possible range
of
such variables as fault currents.
maximum load current, system impedances and other
related factors, where appropriate.
STABILITY
This term, applied to protection as
distinct from power networks, refers to the
ability
of the system to remain inert
to all load conditions and faults external to the
relevant zone.
It is essentially a term
which is applicable to unit systems; the term
'discrimination' is the
equivalent
expression applicable to non-unit systems.
SPEED
The function of
automatic protection is to isolate faults from the
power system in a
very much shorter
time than could be achieved manually, even with a
great deal of
personal supervision. The
object is to safeguard continuity of supply by
removing each
disturbance before it
leads to widespread loss of synchronism, which
would necessitate
the shutting down of
plant.
Loading the system produces
phase displacements between the voltages at
different
points and therefore
increases the probability that synchronism will be
lost when the
system is disturbed by a
fault. The shorter the time a fault is allowed to
remain in the
system, the greater can
be the loading of the system. Figure 1.5 shows
typical relations
between system
loading and fault clearance times for various
types of fault. It will be
noted that
phase faults have a more marked effect on the
stability of the system than does
a
simple earth fault and therefore require faster
clearance.
SENSITIVITY
Sensitivity is a term frequently used
when referring to the minimum operating
current of a complete protective
system. A protective system is said to be
sensitive if the
primary operating
current is low.
When the term is
applied to an individual relay, it does not reter
to a current or
voltage setting but to
the volt-ampere consumption at the minimum
operating current.
A given type of relay element can
usually be wound for a wide range of setting
currents; the coil will have an
impedance which is inversely proportional to the
square of
the setting current value, so
that the volt-ampere product at any setting is
constant. This is
the true measure of
the input requirements of the relay, and so also
of the sensitivity.
Relay power factor
has some significance in the matter of transient
performance .For d.c.
relays the VA
input also represents power consumption, and the
burden is therefore
frequently quoted
in watts.
PRIMARY AND BACK-UP
PROTECTION
The reliability of a power
system has been discussed in earlier sections.
Many
factors may cause protection
failure and there is always some possibility of a
circuit
breaker failure. For this
reason, it is usual to supplement primary
protection with other
systems to 'back-
up' the operation of the main system and to
minimize the possibility of
failure to
clear a fault from the system.
Back-up
protection may be obtained automatically as an
inherent feature of the main
protection
scheme, or separately by means of additional
equipment. Time graded
schemes such as
overcurrent or distance protection schemes are
examples of those
providing inherent
back-up protection; the faulty section is normally
isolated
discriminatively by the time
grading, but if the appropriate relay fails or the
circuit
breaker fails to trip, the next
relay in the grading sequence will complete its
operation and
trip the associated
circuit breaker, thereby interrupting the fault
circuit one section further
back. In
this way complete back- up cover is obtained; one
more section is isolated than
is
desirable but this is inevitable in the event of
the failure of circuit breaker. Where the
system interconnection is more complex,
the above operation will be repeated so that all
parallel infeeds are tripped. If the
power system is protected mainly by unit schemes,
automatic back-up protection is not
obtained, and it is then normal to supplement the
main protection with time graded
overcurrent protection, which will provide local
back-
itz-fgr
itz-fgr
itz-fgr
itz-fgr
itz-fgr
itz-fgr
itz-fgr
itz-fgr
-
上一篇:昨日重现英文歌词含中文翻译
下一篇:鞋类瑕疵常用中英文对照