关键词不能为空

当前您在: 主页 > 英语 >

itz继电保护中英文翻译(精)

作者:高考题库网
来源:https://www.bjmy2z.cn/gaokao
2021-01-28 12:39
tags:

itz-fgr

2021年1月28日发(作者:chinanet是什么)



Fundamentals of protection practice


The purpose of an electrical power system is to generate and supply electrical


energy to consumers. The system should be designed and managed to deliver this energy


to the utilization points with both reliability and economy. As these two requirements are


largely opposed, it is instructive to look at the reliability of a system and its cost and


value to the consumer.


One hand ,The diagram mast make sure the reliability in system design,. On the


other hand, high reliability should not be pursued as an end in itself, regardless of cost,


but should rather be balanced against economy,taking.


Security of supply can be bettered by improving plant design, increasing the spare


capacity margin and arranging alternative circuits to supply loads. Sub-division of the


system into zones. each controlled by switchgear in association with protective gear.


provides flexibility during normal operation and ensures a minimum of dislocation


following a breakdown.


The greatest threat to the security of a supply system is the short circuit,which


imposes a sudden and sometimes violent change on system operation. The large current


which then flows, accompanied by the localized release of a considerable quantity of


energy, can cause fire at the fault location, and mechanical damage throughout the system,


particularly to machine and transformer windings. Rapid isolation of the fault by the


nearest switchgear will minimize the damage and disruption caused to the system.


A power system represents a very large capital investment. To maximize the return


on this outlay. the system must be loaded as much as possible. For this reason it is


necessary not only to provide a supply of energy which is attractive to prospective users


by operating the system ,but also to keep the system in full operation as far as possible


continuously, so that it may give the best service to the consumer, and earn the most


revenue for the supply authority. Absolute freedom from failure of the plant and system




network cannot be guaran- teed. The risk of a fault occurring, however slight for each


item, is multiplied by the number of such items which are closely associated in an


extensive system, as any fault produces repercussions throughout the network. When the


system is large, the chance of a fault occurring and the disturbance that a fault would


bring are both so great that without


equipment to remove faults the system will become, in practical terms, inoperable.


The object of the system will be defeated if adequate provision for fault clearance is not


made. Nor is the installation of switchgear alone sufficient; discriminative protective gear,


designed according to the characteristics and requirements of the power system. must be


provided to control the switchgear. A system is not properly designed and managed if it is


not adequately protected.


Protective gear


This is a collective term which covers all the equipment used for detecting,locating


and initiating the removal of a fault from the power system. Relays are extensively used


for major protective functions, but the term also covers direct-acting and fuses.


In addition to relays the term includes all accessories such as current and voltage


transformers, shunts, a.c. wiring and any other devices relating to the protective


relays.


In general, the main switchgear, although fundamentally protective in its function, is


excluded from the term protective gear, as are also common services, such as the station


battery and any other equipment required to secure opera- tion of the circuit breaker.


Reliablity


The performance of the protection applied to large power systems is frequently


assessed numerically. For this purpose each system fault is classed as an incident and


those which are cleared by the tripping of the correct circuit breakers and only those, are


classed as 'correct'. The percentage of correct clearances can then be determined.




This principle of assessment gives an accurate evaluation of the protection of the


system as a whole, but it is severe in its judgement of relay performance, in that many


relays are called into operation for each system fault, and all must behave correctly for a


correct clearance to be recorded. On this basis, a performance of 94% is obtainable by


standard techniques.


Complete reliability is unlikely ever to be achieved by further improvements in


construction. A very big step, however, can be taken by providing duplication of


equipment or 'redundancy'. Two complete sets of equipment are provided, and arranged


so that either by itself can carry out the required function. If the risk of an equipment


failing is x/unit. the resultant risk, allowing for redundancy, is x2. Where x is small the


resultant risk (x2 may


be negligible.


It has long been the practice to apply duplicate protective systems to busbars, both


being required to operate to complete a tripping operation, that is, a 'two-out-of-two'


arrangement. In other cases, important circuits have been provided with duplicate main


protection schemes, either being able to trip independently, that is, a 'one-out-of- two'


arrangement. The former arrangement guards against unwanted operation, the latter


against failure to operate.


These two features can be obtained together by adopting a 'two-out-of-three'


arrangement in which three basic systems are used and are interconnected so that the


operation of any two will complete the tripping function. Such schemes have already


been used to a limited extent and application of the principle will undoubtedly increase.


Probability theory suggests that if a power network were protected throughout on this


basis, a protection performance of 99.98% should be attainable. This performance figure


requires that the separate protection systems be completely independent; any common




factors, such as common current transformers or tripping batteries, will reduce the overall


performance. SELECTIVITY


Protection is arranged in zones, which should cover the power system completely,


leaving no part unprotected. When a fault occurs the protection is required to select and


trip only the neareat circuit breakers. This property of selective tripping is also called


'discrimination' and is achieved by two general methods:


a Time graded systems


Protective systems in successive zones are arranged to operate in times which are


graded through the sequence of equipments so that upon the occurrence of a fault,


although a number of protective equipments respond, only those relevant to the faulty


zone complete the tripping functiopn. The others make incomplete operations and then


reset.


b Unit systems


It is possible to design protective systems which respond only to fault conditions


lying within a clearly defined zone. This 'unit protection' or 'restricted protection' can be


applied throughout a power system and, since it does not involve time grading, can be


relatively fast in operation.


Unit protection is usually achieved by means of a comparison of quantities at the


boundaries of the zone. Certain protective systems derive their 'restricted' property


from the configuration of the power system and may also be classed as unit protection.


Whichever method is used, it must be kept in mind that selectivity is not merely a matter


of relay design. It also depends on the correct co- ordination of current transformers and


relays with a suitable choice of relay settings, taking into account the possible range of


such variables as fault currents. maximum load current, system impedances and other


related factors, where appropriate.




STABILITY


This term, applied to protection as distinct from power networks, refers to the ability


of the system to remain inert to all load conditions and faults external to the relevant zone.


It is essentially a term which is applicable to unit systems; the term 'discrimination' is the


equivalent expression applicable to non-unit systems.


SPEED


The function of automatic protection is to isolate faults from the power system in a


very much shorter time than could be achieved manually, even with a great deal of


personal supervision. The object is to safeguard continuity of supply by removing each


disturbance before it leads to widespread loss of synchronism, which would necessitate


the shutting down of plant.


Loading the system produces phase displacements between the voltages at different


points and therefore increases the probability that synchronism will be lost when the


system is disturbed by a fault. The shorter the time a fault is allowed to remain in the


system, the greater can be the loading of the system. Figure 1.5 shows typical relations


between system loading and fault clearance times for various types of fault. It will be


noted that phase faults have a more marked effect on the stability of the system than does


a simple earth fault and therefore require faster clearance.


SENSITIVITY


Sensitivity is a term frequently used when referring to the minimum operating


current of a complete protective system. A protective system is said to be sensitive if the


primary operating current is low.


When the term is applied to an individual relay, it does not reter to a current or


voltage setting but to the volt-ampere consumption at the minimum operating current.




A given type of relay element can usually be wound for a wide range of setting


currents; the coil will have an impedance which is inversely proportional to the square of


the setting current value, so that the volt-ampere product at any setting is constant. This is


the true measure of the input requirements of the relay, and so also of the sensitivity.


Relay power factor has some significance in the matter of transient performance .For d.c.


relays the VA input also represents power consumption, and the burden is therefore


frequently quoted in watts.


PRIMARY AND BACK-UP PROTECTION


The reliability of a power system has been discussed in earlier sections. Many


factors may cause protection failure and there is always some possibility of a circuit


breaker failure. For this reason, it is usual to supplement primary protection with other


systems to 'back- up' the operation of the main system and to minimize the possibility of


failure to clear a fault from the system.


Back-up protection may be obtained automatically as an inherent feature of the main


protection scheme, or separately by means of additional equipment. Time graded


schemes such as overcurrent or distance protection schemes are examples of those


providing inherent back-up protection; the faulty section is normally isolated


discriminatively by the time grading, but if the appropriate relay fails or the circuit


breaker fails to trip, the next relay in the grading sequence will complete its operation and


trip the associated circuit breaker, thereby interrupting the fault circuit one section further


back. In this way complete back- up cover is obtained; one more section is isolated than


is desirable but this is inevitable in the event of the failure of circuit breaker. Where the


system interconnection is more complex, the above operation will be repeated so that all


parallel infeeds are tripped. If the power system is protected mainly by unit schemes,


automatic back-up protection is not obtained, and it is then normal to supplement the


main protection with time graded overcurrent protection, which will provide local back-


itz-fgr


itz-fgr


itz-fgr


itz-fgr


itz-fgr


itz-fgr


itz-fgr


itz-fgr



本文更新与2021-01-28 12:39,由作者提供,不代表本网站立场,转载请注明出处:https://www.bjmy2z.cn/gaokao/579429.html

继电保护中英文翻译(精)的相关文章